4 #aan – Measurement Computing CB-COM-7012 User Manual
Page 27
27
CB-7012, CB-7014, CB-7017 User’s Manual
2.4 #AAN
Description: Read Analog Input from channel N
Note: This command is for CB-7017/17F only.
Syntax: #AAN[CHK](cr)
#
Delimiter character
AA
Address for module (00 to FF)
N
channel to read, from 0 to 7
Response:
Valid Command:
>(Data)[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
>
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of responding module (00 to FF)
(Data)
analog input value; see Sec. 1.10 for its format
Example:
Command: #032
Receive: >+02.513
Read Address 03 channel 2, get data successfully.
Command: #029
Receive: ?02
Read Address 02 channel 9, return error channel number.
Related Command:
Sec. 2.1 %AANNTTCCFF, Sec. 2.7 $AA2
Related Topics:
Sec. 1.10 Configuration Tables