38 ~aa1 – Measurement Computing CB-COM-7012 User Manual
Page 61

61
CB-7012, CB-7014, CB-7017 User’s Manual
2.38 ~AA1
Description: Reset Module Status
Syntax: ~AA1[CHK](cr)
~
Delimiter character
AA
Address of module to set (00 to FF)
1
Command to reset module status
Response: Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of responding module (00 to FF)
Example:
Command: ~010
Receive: !0104
Read Address 01 module status, return 04, host watchdog
timeout status is set.
Command: ~011
Receive: !01
Reset Address 01 module status; return successful.
Command: ~010
Receive: !0100
Read Address 01 module status, return 00, host watchdog
timeout status is clear.
Related Command:
Sec.2.36, ~**; Sec.2.37, ~AA0
Related Topic:
Set.3.2, Module Status; Sec.3.3, Dual Watchdog Operation