CB-7012, CB-7014, CB-7017 User’s Manual

2.18 ~AAEV

Description: Enable/Disable Calibration

Syntax: ~AAEV[CHK](cr)

~

Delimiter character

AA

Address of module to set (00 to FF)

E

Command to enable/disable calibration

V

1=Enable/0=Disable calibration

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of responding module (00 to FF)

Example:

Command: $010

Receive: ?01

Perform Address 01 span calibration, returns the command is

invalid before enabling calibration.

Command: ~01E1

Receive: !01

Set Address 01 to enable calibration, return successful.

Command: $010

Receive: !01

Preform Address 01 span calibration, return successful.

Related Command:

Sec. 2.5, $AA0, Sec. 2.6, $AA1

Related Topic:

Sec. 1.9, Calibration