beautypg.com

41 ~aa4 – Measurement Computing CB-COM-7012 User Manual

Page 64

background image

64

CB-7012, CB-7014, CB-7017 User’s Manual

2.41 ~AA4

Description: Read PowerOn Value and Safe Value

Note: This command is for CB-7012/12D/12F/12FD/14D only.

Syntax: ~AA4[CHK](cr)

~

Delimiter character

AA

Address of module to read (00 to FF)

4

Command for reading PowerOn Value and Safe Value

Response: Valid Command:

!AAPPSS[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of responding module (00 to FF)

PP

PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on,

DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

SS

Safe Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1

off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

Example:

Command: ~014

Receive: !010000

Read Address 01 PowerOn/Safe Value, return PowerOn Value

is DO0 off, DO1 off, Safe Value is DO0 off, DO1 off.

Related Command:

Sec. 2.42, ~AA5PPSS

Related Topic:

Set. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation