41 ~aa4 – Measurement Computing CB-COM-7012 User Manual
Page 64

64
CB-7012, CB-7014, CB-7017 User’s Manual
2.41 ~AA4
Description: Read PowerOn Value and Safe Value
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: ~AA4[CHK](cr)
~
Delimiter character
AA
Address of module to read (00 to FF)
4
Command for reading PowerOn Value and Safe Value
Response: Valid Command:
!AAPPSS[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of responding module (00 to FF)
PP
PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on,
DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
SS
Safe Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1
off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
Example:
Command: ~014
Receive: !010000
Read Address 01 PowerOn/Safe Value, return PowerOn Value
is DO0 off, DO1 off, Safe Value is DO0 off, DO1 off.
Related Command:
Sec. 2.42, ~AA5PPSS
Related Topic: