Vari-Flow Air Management System
Temperature Sensors* - installed in hood
• Temperature Sensor T1 to Vari-Flow
(Terminals T1-A, T1-B)
Refer to table (example below) to cross reference the
temperature sensor and the hood mark.
*Repeat based on the number of temperature sensors.
(Terminals T2-A, T2-B | T3-A, T3-B | T4-A, T4-B | T5-
A, T5-B | T6-A, T6-B | T7-A, T7-B | T8-A, T8-B | T9-A,
T9-B | T10-A, T10-B)
Sensors (Field Wiring)
Related Fans
Sensor
Hood Mark
Exhaust Fans
Supply Fans
T1
Hood Mark Name 1
F1-E
F11-S
T2
Hood Mark Name 2
F2-E
F11-S
T3
Hood Mark Name 3
F3-E
F12-S
T4
Hood Mark Name 4
F4-E
F12-S
T5
Hood Mark Name 5
F5-E
F12-S
T6
Hood Mark Name 6
F6-E
F13-S
T7
Hood Mark Name 7
F7-E
F13-S
T8
Hood Mark Name 8
F8-E
F14-S
T9
Hood Mark Name 9
F9-E
F14-S
T10
Hood Mark Name 10
F10-E
F14-S
T1
T1-A
T1-B
T2
T2-A
T2-B
T3
T3-A
T3-B
T4
T4-A
T4-B
T5
T5-A
T5-B
T6
T6-A
T6-B
T7-A
T7-B
T7
T8-A
T8-B
T8
T9-A
T9-B
T9
T10-A
T10-B
T10
Resistive Temperature Detectors (RTD)
Wire the two leads of the sensors to be designated
terminals in the control panel as shown below. This is
determined by the number of temperature sensors on
the job (1-10 sensors). The two wires of the sensor are
not polarity sensitive. If more than one hood is being
controlled, be sure that the appropriate sensor is wired
to the appropriate terminals as depicted on the job
specific wiring diagram.
NOTE
The RTD’s should not be exposed to direct flame. The
RTD’s are rated up to 250°F
CAUTION
Exposing the sensor to direct flame may render the
sensor inoperable and will void the warranty.
Keypad - if equipped
• Connect provided cable from back of keypad to
CAREL® PCO5+ controller (Terminal J10)
PCO5+ J10
KEYPAD
CONNECT FACTORY PROVIDED RJ25 CABLE
TO J10 ON PCO5+ AND BACK OF KEYPAD
35 Foot Cable Provided
75 or 150 Foot Cable is Optional
Touchscreen - if equipped
Power Wiring
• Connect provided 2-wire cable from Vari-Flow
(Terminals 24H, 24C) to touch screen
(Terminals G, GO)
Control Wiring
• Connect provided 3-wire cable from Vari-Flow
(Terminals -, +, GND) to touch screen
(Terminals -, +, GND)
24C
24H
Power Wiring
-
+
GND
Control Wiring
-
+
GND
TOUCH
SCREEN
TOUCH
SCREEN
GO
G
Remote Enable - if used
• Connect remote enable common and normally open
from BMS to Vari-Flow (Terminals RE-1A, RE-1B)
A closed contact will turn on all fans.
An open contact will turn off all fans.
NOTE: Temperature interlock will override the remote
enable input.
RE-1A
RE-1B
NOTE: The Vari-Flow job specific temperature sensor
table is found in the wiring diagram located on the Vari-
Flow panel door. This table is an example, do not use
for your specific job.
®