Installation, Resistive temperature detector(s) (rtd) mounting, Control box mounting – Greenheck Vari-Flow Air Management System(476251) User Manual

Page 3

background image

3

Vari-Flow Air Management System

NOTE

Resistive temperature detector(s) may be factory
installed. If so, continue to the next section.

Resistive Temperature Detector(s)
(RTD) Mounting

1. Locate flat area(s) at the top interior of the hood in

front of the filters, towards the front of the hood.

3. Center the octagon extension over the hole on the

hood surface.

2. Cut a 3/4-inch diameter hole into the top of the

capture tank. Make sure the resistive temperature
detector(s) will not interfere with fire system nozzles
and is not within 12 inches of light fixtures.

Installation

Control Box Mounting

1. Locate an area with enough space to mount the

control box and fasten to the wall.

NOTE

All field installation and wiring of electrical equipment
must be done to meet NEC and local codes.

.75 to .875 inch
diameter hole

Hood
Surface

4. Insert the compression seal into the hole from

the inside of the hood making sure the gasket is
placed on the fitting before inserting it into the hole.
Place the octagon box and J-box plate provided
over the fitting on the top of the hood, keeping the
fitting centered in the box. Install the lock washer
and 1-1/2 inch nut on the threaded portion of the
compression seal and tighten securely.

1/4 inch Compression Seal

Gasket

J-Box Plate

Temperature
Sensor

Lock Washer

Nut

Octagon Cover

5. Insert the resistive temperature detector (RTD) into

compression seal and tighten to 35 ft-lbs.

6. Place octagon cover onto J-box plate and fasten it.

NOTE

Control Box may be factory mounted. If so, continue
to the next section.

NOTE

If the Vari-Flow system is equipped with static
pressure controls it will be located in the Vari-Flow
cabinet, therefore this control box should be mounted
in the space to be controlled. If the control box is
mounted outside of this space, please refer to the
Pneumatic Static Pressure Kit Installation Instructions.

Octagon
Extension

Exhaust Area

Supply Area (optional)

Sensor Install

Cut Out Area

Top View of Exhaust Hood

®