background image

19

Vari-Flow Air Management System

T

HIS

SCREEN

ALLOWS

THE

USER

TO

ADJUST

BAC

NET

MSTP

PARAMETERS

.

This screen only appears if the selected BMS protocol is set to BACnet MSTP and
BACnet Plugin = YES.

If a BACnet MSTP card has been installed, the default parameters can be changed
via the controller display. Factory settings are shown in the screen to the left.

To view current parameters:

1. Power on controller and allow several minutes to initialize.

2. Go to BMS Config menu and view BACnet Read/Write screen.

3.

Change

Function to Read and Update? to YES.

Current BACnet MSTP parameters should now be displayed in the BACnet MSTP
SETUP screen. If all values appear to be zeros, consult the factory. (Make sure you
have allowed several minutes for the controller to initialize).
Values may appear to be zero prior to setting the Function to READ.

To change BACnet MSTP parameters:

1. Power on controller and allow several minutes to initialize.

2. Go to BMS Config menu and view MSTP SETUP screen.

3.

Move cursor to desired parameter by pressing the buttons. Press

to select the parameter to change. Press the buttons to adjust the
parameter. Press

to save adjusted value.

4.

Once desired parameters have been entered, go to BACnet Read/Write
screen. Change Function to Write and Update? to YES.

5.

Reboot the controller by cycling power to the unit. Allow several minutes for
the controller to initialize.

6. View MSTP parameters. If changed values did not save, contact the factory.

MSTP SETUP

Instance: 77000

Baudrate 38400
MAC Addr:

0

MaxMasters: 127
MaxInfoFrames: 20

BACnet Read/Write

Function: Read

Update? Yes

*Cycle unit power to confirm
write command.

T

HIS

SCREEN

ALLOWS

THE

USER

TO

ADJUST

BAC

NET

IP

PARAMETERS

.

This screen only appears if the selected BMS protocol is set to BACnet IP/Eth and
BACnet Plugin = YES.

If a BACnet IP card has been installed, the default parameters can be changed
via the controller display. The card is in DHCP mode from the factory. Once
communication is established, the user can enter static IP parameters.

To view current parameters:

1. Power on controller and allow several minutes to initialize.

2. Go to BMS Config menu and view BACnet Read/Write screen.

3.

Change

Function to Read and Update? to YES.

Current BACnet IP parameters should now be displayed in the BACnet TCP/IP
SETUP screen. If all values appear to be zeros, consult the factory. (Make sure you
have allowed several minutes for the controller to initialize).
*Values may appear to be zero prior to setting the Function to READ.

To change BACnet TCP/IP parameters:

1. Power on the controller and allow several minutes to initialize.

2. Go to BMS Config menu and view TCP/IP SETUP screen.

3.

Move cursor to desired parameter by pressing the buttons. Press

to select the parameter to change. Press the buttons to adjust the
parameter. Press

to save adjusted value.

4.

Once desired parameters have been entered, go to BACnet Read/Write
screen. Change Function to Write and Update? to YES.

5.

Reboot the controller by cycling power to the unit. Allow several minutes for
the controller to initialize.

6. View TCP/IP parameters. If changed values did not save, contact the factory.

TCP/IP SETUP

Instance: 77000

IP set by:

DHCP

IP: 128.2.104.134
Subnet: 255.255.000.000
Gatewy: 128.2.0.12

TCP/IP SETUP

DNS 1:

193.168.001.001

DNS 2:

193.168.001.001

Type: IP

BACnet Read/Write

Function: Read

Update? Yes

*Cycle unit power to confirm
write command.

®