beautypg.com

Line load, Line, Load – Greenheck Vari-Flow Air Management System(476251) User Manual

Page 6: Modbus vfd, Vfd by others, Va ri-green mot o r

background image

6

Vari-Flow Air Management System

Variable Frequency Drives (VFD) - if equipped

NOTE

If electrically commutated motors are being used,
VFDs will not be needed.

1. Bring power to the input of each VFD from a

dedicated power source using conduit to the
NEMA-1 enclosure on the bottom of the drive. Each
power source shall be of the same voltage as the
respective fan and of a high enough amp rating to
handle the full load amp draw of the respective fan.

2. To avoid interference between the conductors,

separate conduit from the VFD output to the input
power of the fan must be used for each fan.

NOTE

The VFD motor overload parameter (E2-01) need to
be set to the motor nameplate FLA. Refer to the Quick
Start Guide from Yaskawa (pages 83-89) for setting
these parameters on the Yaskawa drive.

NOTE

Be sure to use appropriately sized wire for the full load
amp draw.

VFD Provided by Others, Control Wiring - if equipped

• Fault command from Vari-Flow to VFD provided by

others (Terminal E__-FA, E__-FB)

• Run command from Vari-Flow to VFD provided by

others (Terminal E__-RA, E__-RB)

• Speed reference from Vari-Flow to VFD provided by

others (Terminal E__S+, E__S-)

• Line power to VFD

• Load power from VFD to fan

This is an example of Exhaust Fan 1 provided with a VFD by others.

L3

COMMON

L2

L1

T3

T2

T1

NORMALLY OPEN

RUN COMMAND

RUN COMMAND

SPEED REFERENCE +

E1-FA

E1-FB

E1-RA

E1-RB

E1-S+

E1-S-

VFD-F1-E

MARK: VFD BY

OTHERS
VOLT/PH

HP

VFD BY OTHERS

LINE

LOAD

SPEED REFERENCE -

FAULT CONTACT

VFD BY

OTHERS

S+

S-

R+

L3

LINE

R-

IG

L2

L1

T3

LOAD

T2

T1

VFD-F1-E

MARK: FAN MARK

VOLT/HP

MODBUS VFD

ADDRESS: X

S2

Each variable frequency drive must have the

LINE and LOAD wiring in separate conduit

MODBUS VFD

OFF

Vari-Green® Fan Wiring - if equipped

• 24 VAC from Vari-Flow to Vari-Green motor control

wire, black (Terminal E__-24)

• 0-10 VDC Speed Reference from Vari-Flow to

Vari-Green motor control wire, red (Terminal E__S+)

• Common from Vari-Flow to Vari-Green motor control

wire, white (Terminal E__S-)

This is an example of Exhaust Fan 1 provided with a Vari-Green motor.

G

LINE

N

H

VFD-F1-E

MARK: VG

115/1

0.75 HP

VARI-GREEN

24 VAC RUN (BLACK)

SPEED REF. + (RED)

SPEED REF. - (WHITE)

NOTE: POWER FOR THE

VARI-GREEN FAN GOES
DIRECTLY TO FAN

E1-24

E1-S+

E1-S-

V

A

RI-GREEN MOT

O

R

®