Vari-Flow Air Management System

The I/O Configuration menu allows adjustment of all controller inputs and outputs.
This menu is similar to the Probe Adjustment menu, except that it additionally allows
adjustment of the factory default ‘normal’ states of the digital inputs and the direction
of the analog outputs. Additionally, it allows adjustment of the physical location
of each I/O. ADJUSTMENT OF I/O PHYSICAL LOCATION MUST ONLY BE DONE
UNDER FACTORY GUIDANCE! IMPROPER ADJUSTMENT MAY RESULT IN SYSTEM
DAMAGE!

This is an example of an analog input configuration screen.

In the I/O configuration screens, the user can alter the physical location and type
of each point.

Similar configuration screens appear for the remaining I/O.

Analog Input

Temperature 1
En: ON

Ch: 1

Normal PT1000

Offset: 0.0°F
Value: 70.5°F

Analog Input

Temperature 1
En: ON

Ch: 1

Normal PT1000

Offset: 0.0°F
Value: 70.5°F

Digital Input

Remote On/Off
Enable; ON Channel:

1

Action: CLOSED
Delay: 0s
Status: Open

Analog Output Config

Enable: ON
Channel: 1
Action: DIRECT

Minimum: 0.0vdc
Maximum: 10.0vdc

Relay Output

Enable: ON
Channel: 1
Status: OFF

H.

Manufacturer

b. I/O Configuration

Initialization

DEFAULT INSTALLATION
Erase user settings and install
global default values:

NO

T

HIS

SCREEN

ALLOWS

THE

USER

TO

RESTORE

BACK

TO

THE

ORIGINAL

F

ACTORY

DEFAULT

PARAMETERS

.

Restoring to the original default parameters will result in a non-customized
controller. The user should not restore to these settings unless instructed by the
factory.

The Initialization Menu allows the user to save and restore the controllers default
parameters. The controller can be restored with either the Manufacturer’s default
parameters from shipment, or an unconfigured factory default.

T

HIS

SCREEN

ALLOWS

THE

USER

TO

SAVE

AND

RESTORE

THE

FACTORY

DEFAULT

PARAMETERS

STORED

IN

MEMORY

.

The Factory Settings include the Factory default parameters and the unit setup
code. If the user would like to restore to these parameters, move the cursor to the
Restore position and change to ON.

Factory Save

Save? OFF
Restore? OFF
Auto Restore?

No

T

HIS

SCREEN

ALLOWS

THE

USER

TO

CLEAR

ALL

SAVED

DATA

.

Factory Delete

CLEAR ALL SAVED DATA
FACTORY+USER: OFF

T

HIS

SCREEN

ALLOWS

THE

USER

TO

SAVE

AND

RESTORE

THE

USER

PARAMETERS

STORED

IN

MEMORY

.

The User Settings include the Factory default parameters. If the user would like to
restore to these parameters, move the cursor to the Restore position and change
to ON.

User Save

Save? OFF
Restore? OFF
Auto Restore?

No

H.

Manufacturer

d. Initialization

T

HIS

SCREEN

ALLOWS

THE

USER

TO

CHANGE

THE

S

ERVICE

(PW1)

AND

M

ANUFACTURER

P

ASSWORD

(PW2).

Passwords

Insert new passwords
Service (PW1):

0000

Manufacturer (PW2): 0000

®