System optimization – Greenheck Vari-Flow Air Management System(476251) User Manual
Page 12
12
Vari-Flow Air Management System
System Optimization
Low Temperature Set Point (90°F default)
Record the kitchen ambient temperature ___________
Set the low temperature set point 5°F above the
ambient kitchen temperature
Setting the Low Temperature Set Point
NOTE: If the system is provided with a keypad, press
the Prg button (
) for 5 seconds to enter the main
menu.
1. Go to Setpoints menu.
2. Go to Exhaust Fan Setup on page 16.
3. Adjust the Low Temp Setpoint to the previously
recorded value.
High Temperature Set Point (115°F default)
1. Turn the fans on by pressing the ‘FAN’ button on the
keypad.
2. Turn on all cooking appliances and allow them to
reach normal cooking temperatures.
3. Record the temperature in the hood by looking at the
temperature in the main menu. __________
4. Set the high temperature set point 5°F below the
previously recorded temperature.
Setting the High Temperature Set Point
NOTE: If the system is provided with a keypad press
the Prg button (
) for 5 seconds to enter the main
menu.
1. Go to Setpoints menu.
2. Go to Exhaust Fan Setup on page 16.
3. Adjust the High Temp Setpoint to the previously
recorded value.
4. Press ESC until you reach the keypad indicators on
the LCD screen.
®