Vari-Flow Air Management System

System Optimization

Low Temperature Set Point (90°F default)

Record the kitchen ambient temperature ___________

Set the low temperature set point 5°F above the
ambient kitchen temperature

Setting the Low Temperature Set Point

NOTE: If the system is provided with a keypad, press
the Prg button (

) for 5 seconds to enter the main

menu.

1. Go to Setpoints menu.

2. Go to Exhaust Fan Setup on page 16.

3. Adjust the Low Temp Setpoint to the previously

recorded value.

High Temperature Set Point (115°F default)

1. Turn the fans on by pressing the ‘FAN’ button on the

keypad.

2. Turn on all cooking appliances and allow them to

reach normal cooking temperatures.

3. Record the temperature in the hood by looking at the

temperature in the main menu. __________

4. Set the high temperature set point 5°F below the

previously recorded temperature.

Setting the High Temperature Set Point

NOTE: If the system is provided with a keypad press
the Prg button (

) for 5 seconds to enter the main

menu.

1. Go to Setpoints menu.

2. Go to Exhaust Fan Setup on page 16.

3. Adjust the High Temp Setpoint to the previously

recorded value.

4. Press ESC until you reach the keypad indicators on

the LCD screen.

®