Settings - continued, Vari-flow air management system – Greenheck Vari-Flow Air Management System(476251) User Manual
Page 27

27
Vari-Flow Air Management System
FIRE SETTINGS
DO NOT CHANGE THE ABOVE SETTINGS AFTER THE FIRE TEST HAS BEEN
COMPLETED.
LIGHTS OUT IN FIRE
NO
EXHAUST IN FIRE
OFF
ELECTRIC GAS VALVE PRESENT
NO
FIRE SETTINGS
DO NOT CHANGE THE ABOVE SETTINGS AFTER THE FIRE TEST HAS BEEN
COMPLETED.
LIGHTS OUT IN FIRE
NO
EXHAUST IN FIRE
OFF
ELECTRIC GAS VALVE PRESENT
NO
SUPPLY FAN
SETTINGS HOME
SUPPLY FAN 1 DETAILS
VFD BY OTHERS OR VARI-
GREEN MOTOR USED. NO
FURTHER INFORMATION
AVAILABLE.
FAN NAME:
SUP 1
DESIGN CFM
4800
CURRENT CFM
0
LOW SPEED
50.0
%
HIGH SPEED
100.0 %
EXHAUST FANS CONTROLLING THIS SUPPLY FAN
1 2 3 4
SUPPLY FAN
SETTINGS HOME
SUPPLY FAN 1 DETAILS
VFD BY OTHERS OR VARI-
GREEN MOTOR USED. NO
FURTHER INFORMATION
AVAILABLE.
FAN NAME:
SUP 1
DESIGN CFM
4800
CURRENT CFM 0
LOW SPEED 50.0
%
HIGH SPEED 100.0
%
EXHAUST FANS CONTROLLING THIS SUPPLY FAN
1 2 3 4
Settings - continued
Supply Fan allows the user to change the setpoints for
the fan.
Fan Name: User can adjust the “nickname” of the fan
to something such as “SUP1”.
Design CFM: Set from factory (full speed airflow rate)
Current CFM: Current estimated supply airflow.
Low Speed: Lowest speed the fan can run at.
High Speed: Highest speed the fan can run at.
Exhaust Fans Controlling this Supply Fan: Shows
which exhaust fans are controlling this fan speed.
Lights allows the user to adjust the names of the light
circuits.
Temp Interlock: Allows the user to change the
setpoints of the temperature interlock setpoints.
Temperature Interlock Enabled: Enables/disables
the temperature interlock feature. Used to meet
IMC 507.2.1.1. DO NOT CHANGE THIS ONCE THE
SYSTEM HAS PASSED INSPECTION.
Temperature On: The temperature at which the fan(s)
automatically turn on.
Temperature Off: The temperature at which the fans(s)
will turn off once the time delay setpoint is reached.
Time Delay Setpoint: Amount of time the fan(s) need
to be below the temperature off setpoint before the
fan(s) will shut off.
100% Override Timer: Amount of time the fans are
overridden when the 100% override button is pressed.
Fire allows the user to adjust the fire system settings.
Lights Out in Fire: Setting for what the hood lights are
to do in fire.
Exhaust in Fire: Setting for what the exhaust fans
should do in a fire.
Electric Gas Valve Present: Setting for whether there
is a electric gas valve being controlled by the Vari-Flow.
NOTE
The fans will modulate speed based on the exhaust
fans assigned to this supply fan.
TEMPERATURE INTERLOCK SETTINGS
TEMPERATURE INTERLOCK ENABLED
YES
TEMPERATURE ON SETPOINT
115
°F
TEMPERATURE OFF SETPOINT
90
°F
TIME DELAY OFF SETPOINT
10
MINUTES
100% OVERRIDE BUTTON TIMER
10
MINUTES
TEMPERATURE INTERLOCK SETTINGS
TEMPERATURE INTERLOCK ENABLED
YES
TEMPERATURE ON SETPOINT
115
°F
TEMPERATURE OFF SETPOINT
90
°F
TIME DELAY OFF SETPOINT
10
MINUTES
10
10
100% OVERRIDE BUTTON TIMER
10
MINUTES
10
10
LIGHT CIRCUIT 1 NAME:
SYSTEM 1
LIGHT CIRCUIT 2 NAME:
SYSTEM 2
LIGHT CIRCUIT 3 NAME:
SYSTEM 3
LIGHT CIRCUIT 4 NAME:
SYSTEM 4
LIGHT SETTINGS
LIGHT CIRCUIT 1 NAME:
SYSTEM 1
LIGHT CIRCUIT 2 NAME:
SYSTEM 2
LIGHT CIRCUIT 3 NAME:
SYSTEM 3
LIGHT CIRCUIT 4 NAME:
SYSTEM 4
LIGHT SETTINGS
®