Settings, General information, Vari-flow air management system – Greenheck Vari-Flow Air Management System(476251) User Manual
Page 26

26
Vari-Flow Air Management System
FAN 1
HOOD 1
FAN 2
HOOD 2
FAN 3
HOOD 3
FAN 4
HOOD 4
INDIVIDUAL FAN CONTROL
FAN 1
HOOD 1
FAN 2
HOOD 2
FAN 3
HOOD 3
FAN 4
HOOD 4
INDIVIDUAL FAN CONTROL
LIGHTS 1
SYSTEM 1
LIGHTS 2
SYSTEM 2
LIGHTS 3
SYSTEM 3
LIGHTS 4
SYSTEM 4
INDIVIDUAL LIGHT CONTROL
LIGHTS 1
SYSTEM 1
LIGHTS 2
SYSTEM 2
LIGHTS 3
SYSTEM 3
LIGHTS 4
SYSTEM 4
INDIVIDUAL LIGHT CONTROL
Individual light control directs you to the
individual light control page where you can
turn individual lights on or off.
Individual fan control directs you to the
individual light control page where you can
turn individual fans on or off.
Navigation icon will display a submenu
showing alarms, home and settings.
INDIVIDUAL
LIGHT ON/OFF
INDIVIDUAL
LIGHT ON/OFF
INDIVIDUAL
FAN ON/OFF
INDIVIDUAL
FAN ON/OFF
T FAN
50
25
0
SUP
T FAN
FA
50
25
0
SUP
SU
Alarm directs you to the alarms page.
Home directs you to the HOME page (current page shown).
Settings directs you to the main settings page.
Pressing to the left or right side of the ALARM - HOME -
SETTINGS will hide those buttons.
Back arrow returns you to the previous screen.
EXHAUST FANS
SUPPLY FANS
LIGHTS
TEMP INTERLOCK
FIRE
BALANCING
SCHEDULE
BMS
TEMP SENSORS
TRENDING
ALARMS
INFORMATION
SETTINGS, CONFIGURATION & INFORMATION
SETTINGS
CONFIGURATION
INFORMATION
EXHAUST FANS
SUPPLY FANS
LIGHTS
TEMP INTERLOCK
FIRE
BALANCING
SCHEDULE
BMS
TEMP SENSORS
TRENDING
ALARMS
INFORMATION
SETTINGS, CONFIGURATION & INFORMATION
SETTINGS
CONFIGURATION
INFORMATION
EXHAUST FAN 1 DETAILS
TEMPERATURE SENSORS ASSIGNED TO THIS FAN
EXHAUST FAN
SETTINGS HOME
VFD BY OTHERS OR VARI-
GREEN MOTOR USED. NO
FURTHER INFORMATION
AVAILABLE.
FAN NAME:
HOOD 1
DESIGN CFM
3000
CURRENT CFM
0
LOW TEMP SETPOINT
90
°F
HIGH TEMP SETPOINT
115
°F
LOW SPEED
50.0
%
HIGH SPEED
100.0 %
1 2 3 4
EXHAUST FAN 1 DETAILS
TEMPERATURE SENSORS ASSIGNED TO THIS FAN
EXHAUST FAN
SETTINGS HOME
VFD BY OTHERS OR VARI-
GREEN MOTOR USED. NO
FURTHER INFORMATION
AVAILABLE.
FAN NAME:
HOOD 1
DESIGN CFM
3000
CURRENT CFM
0
LOW TEMP SETPOINT
90
°F
90
90
HIGH TEMP SETPOINT
115
°F
115
115
LOW SPEED
50.0
%
50.0
50.0
HIGH SPEED
100.0 %
100.0
100.0
1
2
3
4
Settings
Exhaust Fans allows the user to change the setpoints
for the fan.
Fan Name: User can adjust the “nickname” of the fan
to something such as “HOOD1”.
Design CFM: Set from factory (full speed airflow rate).
Low Temp Setpoint: Temperature at which the speed
of the fan is at the low speed.
High Temp Setpoint: Temperature at which the speed
of the fans is at the high speed.
Low Speed: Speed at which the fan is at when at or
below the low temp setpoint.
High Speed: Speed at which the fan is at when at or
above the high temp setpoint.
Temperature Sensors Assigned: Shows which
temperature sensors are controlling this fan speed.
NOTE
The fans will modulate speed when the temperature is
between the low and high temp setpoints.
General Information
Any field that has a black border with a green fill,
indicates it is editable.
If the field displays a numerical value, a number keypad
will display. After entering the desired value press the
Enter button.
If the field is an alphanumeric value, a standard
keyboard will display. After entering the desired value,
press the Enter button.
The field may also display a multiple choice. After