Vari-Flow Connection Checklist

Power for Vari-Flow Cabinet
… Connect 115 VAC power for controls (Terminals H, N)
… Connect 115 VAC power for hood lights, one per light

circuit (Terminals H1, N1 | H2, N2 | H3, N3 | H4, N4)

… Connect 115 VAC power to lights, one per light circuit

(Terminals B1, W1 | B2, W2 | B3, W3 | B4, W4)

Power to Variable Frequency Drives (VFD)*
… Line power to VFD input, bottom left of VFD

(Terminals L1, L2, L3)

… Load power from VFD output, bottom right of VFD

(Terminals T1, T2, T3)

Vari-Green® Fan Wiring* - if equipped
… 24 VAC from Vari-Flow to Vari-Green motor control wire,

black (Terminal E__-24)

… 0-10 VDC Speed Reference from Vari-Flow to Vari-Green

motor control wire, red (Terminal E__S+)

… Common from Vari-Flow to Vari-Green motor control wire,

white (Terminal E__S-)

VFD Provided by Others, Control Wiring* - if equipped
… Fault command from Vari-Flow to VFD provided by others

(Terminal E__-FA, E__-FB)

… Run command from Vari-Flow to VFD provided by others

(Terminal E__-RA, E__RB)

… Speed reference from Vari-Flow to VFD provided by others

(Terminal E__S+, E__S-)

… Line power to VFD
… Load power from VFD to fan

Make-Up Air VFD in Vari-Flow Wiring* - if equipped

… 24 VAC run command from Vari-Flow to make-up air unit

(Terminals S__-42, S__-43)

… Tempering status from Vari-Flow to make-up air unit

(Terminals S__-44, S__-45)

… Line power to VFD input, bottom left of VFD

(Terminals L1, L2, L3)

… Load power from VFD output, bottom right of VFD to make-

up air disconnect (Terminals T1, T2, T3)

Make-Up Air VFD in Make-Up Air Wiring* - if equipped
… 24 VAC run command from Vari-Flow to make-up air unit

(Terminals S__-42, S__-43)

… Tempering status from Vari-Flow to make-up air unit

(Terminals S__-44, S__-45)

… 0-10 VDC speed reference from Vari-Flow to make-up air

unit (Terminals S__-46, S__-47)

Auto Tempering - if equipped
… Auto Heat/Cool enable

(Terminals S1-R, S1-W1, S1-Y1)

Fire System Microswitch

… Fire system microswitch common to Vari-Flow (Terminal C1)
… Fire system microswitch normally closed contact to

Vari-Flow (Terminal NC1)

Resistive Temperature Sensors* - installed in hood
… Temperature Sensor T1 (Terminals T1-A, T1-B)

If more than one temperature sensor is used, wire the

following if applicable:
… Temperature Sensor T2 (Terminals T2-A, T2-B)
… Temperature Sensor T3 (Terminals T3-A, T3-B)
… Temperature Sensor T4 (Terminals T4-A, T4-B)
… Temperature Sensor T5 (Terminals T5-A, T5-B)
… Temperature Sensor T6 (Terminals T6-A, T6-B)
… Temperature Sensor T7 (Terminals T7-A, T7-B)
… Temperature Sensor T8 (Terminals T8-A, T8-B)
… Temperature Sensor T9 (Terminals T9-A, T9-B)
… Temperature Sensor T10 (Terminals T10-A, T10-B)

Keypad - if equipped

… Connect provided RJ25 cable from back of keypad to

CAREL® PCO5+ (Terminal J10).

Touch Screen - if equipped

… Connect provided 2-wire cable from Vari-Flow

(Terminals 24H, 24C) to touch screen (Terminals G, GO)

… Connect provided 3-wire cable from Vari-Flow

(Terminals -, +, GND) to touch screen (Terminals -, +, GND)

Remote Enable- if used
…

Connect remote enable common and normally open from
BMS to Vari-Flow (Terminals RE-1A, RE-1B)

Shunt Trip - if used

… 115 VAC from Vari-Flow to shunt trip breaker coil (provided

by others) (Terminals STH, STN)

Electric Gas Valve with Gas Reset - if equipped
… 115 VAC from Vari-Flow to gas solenoid

(Terminals SVH, SVN)

Spare Fire Relay Contacts - if equipped

… Power to common (Terminal C3)
… Power out, normally open, closed in fire (Terminal NO3)
… Power out, normally closed, open in fire (Terminal NC3)
… Power to common (Terminal C4)
… Power out, normally open, closed in fire (Terminal NO4)
… Power out, normally closed, open in fire (Terminal NC4)

High Temperature Alarm Contacts - if equipped

… Power to common (Terminals HT-C)
… Power out, normally closed, open in high temperature alarm

(Terminal HT-NC)

… Power out, normally open, closed in high temperature alarm

(Terminal HT-NO)

Air Proving Switch(es) (provided by others) - if equipped

… Common and normally open from supply fan 1 air proving

switch to Vari-Flow (Terminals AP-1A, AP-1B)

… Common and normally open from supply fan 2 air proving

switch to Vari-Flow (Terminals AP-2A, AP-2B)

… Common and normally open from supply fan 3 air proving

switch to Vari-Flow (Terminals AP-3A, AP-3B)

… Common and normally open from supply fan 4 air proving

switch to Vari-Flow (Terminals AP-4A, AP-4B)

Wash Interface - if equipped

… Wash input from waterwash control panel (WWCP) to

Vari-Flow (Terminals WI-1A, WI-1B)

… Wash output from Vari-Flow to Grease Grabber H

2

O or

WWCP (Terminals WO-1A, WO-1B)

… Low detergent input from Grease Grabber H

2

O or WWCP to

Vari-Flow (Terminals WD-1A, WD-1B)

* Wiring repeated based on the number of

fans of that type. This is based on the job
specific Vari-Flow wiring diagram.

®