2. tools and accessories, 3. locations, 4. safety limitations – Gasboy Tag Reader User Manual
Page 18: 2. tools, Accessories, 4. safety, Limitations

Tag Reader Installation Guide
14
2-2.
2-2.
TOOLS
AND
ACCESSORIES
TOOLS AND ACCESSORIES
Tag Reader can be provided with an installation kit for the Tag Reader, which includes a rubber
seal, P/N 8149-27400, and four M4 × 20 screws, P/N 8152-03120, with spring washers.
No special tools are required for installing the Tag Reader. Make sure you have 4 mm, 4.4 mm and
5mm drill bits.
2-3.
2-3.
LOCATIONS
LOCATIONS
The Tag Reader can be installed in several Unclassified/Non-Hazardous Locations:
Attached to a station controller box (CFN PLUS) and Over Class 1 Division 2 Group D
Attached to a Tanker Truck controller box and Over Class 1 Division 2 Group D
On a pole or wall mounted close to the station dispensers.
Connected to the station controller box (CFN PLUS) in the station office or in any other
non-explosive environment.
If no suitable walls or poles are available, the Tag Reader can be installed on a dedicated
pole. In that case, setting the pole in the island must comply with the UL/EU or any local
regulations requirements such as cementing the pole to the island floor, laying cables and
keeping the Tag Reader Box outside Class I zone, as described in paragraph 2-4.
Inside the driver compartment of a tanker truck
N
N
O
O
T
T
E
E
Maximum distance of the RS-485 communication
line between Tag Reader and Controller box is 330
feet (100m).
More than one Tag Reader can be mounted in one station for improved service. In this case all Tag
Readers shall be connected to the same, single CFN PLUS via RS-485.
The preferred installation method depends on the layout and configuration of the gas station. Any of
the above selected methods must comply with UL and EU requirements.
C
C
A
A
U
U
T
T
I
I
O
O
N
N
The Tag Reader must NOT be installed on the
dispenser or in any other hazardous environment.
2-4.
2-4.
SAFETY
LIMITATIONS
SAFETY LIMITATIONS
Due to safety requirements, the Tag Reader box can be installed only in non-hazardous areas/
non-classified area. Hazardous areas are shown in grey in the control drawing (see Figure 2-2).
Therefore, the Tag Reader must be installed within the following boundaries: