beautypg.com

Gasboy Fuel Point Reader User Manual

Page 30

background image

GASBOY Fuel Point System

4-4

03/28/03

Attaching the FPR to all FleetKey Pedestals, or to CFN Pedestal with Built-in Pump Control
Unit

WARNING:

Before proceeding, move the GASBOY fuel management system/island
reader unit to a safe location away from the fueling island.

This procedure assumes the fuel management system was installed according to the applicable
codes and according to the specifications set forth in the GASBOY fuel management system
Installation Manual. Be sure to follow these same restrictions and guidelines when re-installing
the FMS back onto the island.

1.

Turn off all breakers supplying power to the Fuel Management System pedestal, including
breakers supplying power to pumps that are controlled through the pedestal. Remove the
pedestal's side access covers. Mark and detach all wiring coming from the pedestal
conduits. Unbolt and remove the pedestal from the island. Take the pedestal to a safe
location away from the fuel island.

2.

Measure the height of the internal barrier plate and mark a horizontal line on the outside of
the pedestal as shown. Measure to the center of the pedestal and mark a vertical line as
shown. Using the measurements from the diagram below, mark and drill four mounting
holes. For the conduit hole, drill a pilot hole, then finish with a 1-1/8" diameter punch.

3.

Hold the FPR against the rear of the pedestal to make sure the five holes line up. Attach the
FPR using the four 051790 bolts, 068891 lock washers, 068005 flat washers, C08875 gasket
washers, and 038860 nuts as shown on page 4-6. The steel washers are used on the
outside, under the bolt head and the gasket washers go between the FPR brackets and FMS
pedestal.

4.

Proceed to Completing the FPR Mounting - All Pedestal Types.