MDE-4556 Gasboy ATC Kits M06875K00X Installation Manual • July 2006

Programming the ATC Option

Switch ON the programming switch located on ATC Controller board (

Figure 5 on page 12

).

At power up:

• Programmed units will flash “104” and then, normal information.
• Non-programmed units will flash “100” which indicates the units must be programmed

per

How To Program Each Fueling Position

below.

How To Program Each Fueling Position

Note: If programming switch is set to OFF, this procedure will not work.

1

Press 1 0 0.

2

Press ENTER.

Money Position will display “1”.
Money Position shows which meter is selected.
(Meter: 1 through 8)

Volume Position will display “1”.
Volume Position shows which fuel type has been selected.
(Fuel Type: 1-gasoline, 2-diesel)

PPU Position will display “730”.
PPU Position shows which fuel density has been selected for the corresponding meter.
[Fuel Density (kg/m

3

): gasoline-730, diesel-840]

Note: The Fuel Density default is 730.

The software will sequence through each meter position for you to assign the fuel type desired.

3

Select fuel type and press ENTER.

4

Sequence through each meter position and verify desired fuel type by pressing ENTER.

5

Switch OFF the programming switch on ATC controller board (

Figure 5 on page 12

).

6

Press F2 to exit ATC programming mode.

7

Weights and Measures auditor will put a seal on the programming switch (

Figure 5

).

8

Close electronics door.

1

730

1

PPU Position:

Main Display

Information

Money Position:
Current Meter

Volume Position:
Fuel Type

Fuel Density