MDE-4333E Atlas Fuel Systems Site Preparation Manual · November 2011

Page 35

Plumbing Requirements

Site Preparation

Connecting the Vapor Return Line to the Vapor Shear Valve

Do not create any liquid traps when connecting the vapor return line to the vapor line Shear
Valve (see

Figure 3-9

on

page 35

). A liquid trap is a low spot in the vapor return line that can

accumulate fuel and cause blockage, which could cause a system to fail vapor recovery
certification tests or create operation issues with vapor balance nozzles.

Notes: 1) The contractor must provide and install the pipe union for connecting to the

1-inch NPT coupling in the unit.

2) Follow the vapor Shear Valve’s manufacturer information regarding mounting of the

Shear Valve to the unit.

Figure 3-9: Correct Vapor Line Connection Method

Correct

Do not allow Liquid Traps

No place for liquid to
be trapped

Not Allowed

1-inch NPT Vapor Return Pipe
supplied in the Unit

Contractor-supplied
Fittings, Pipe, and Shear
Valve

Contractor-supplied
Fittings, Pipe, and
Shear Valve

Vapor Line Shear Valve