beautypg.com

Circuit breakers, Stp control relay boxes for dispensers – Gasboy Atlas Fuel Systems Site Prep Manual User Manual

Page 18

background image

Site Preparation

Electrical Requirements

Page 14

MDE-4333E Atlas Fuel Systems Site Preparation Manual · November 2011

Circuit Breakers

Figure 3-1: Circuit Breakers

Do not Use

Use

• Install a dedicated UL/ULC/CSA-listed switched-neutral breaker to each circuit leading to

a pump/dispenser or dispenser and STPs. It must be able to disconnect hot and neutral
conductors simultaneously. Single-pole breakers with handle ties must not be permitted.
Ref. NEC 514.11 (Switched Neutral is not allowed in Canada).

• Use only UL/ULC/CSA-listed circuit breaker panel as appropriate for that area.
• Install circuit breakers away from the pumps/dispensers. They must be readily accessible

and clearly marked.

• Install a separate circuit breaker for each STP (dispenser models) or each pump motor

(self-contained models).

• Install one circuit breaker for each pump/dispenser or small island group to allow

powering down of pump/dispenser for service.

Power to the unit must be supplied from a dedicated breaker.

• No other equipment must be powered from this breaker.
• Remote dispensers may be grouped together on a single breaker when the submersible

pump has its own breaker.

• It is recommended that no more than two remote dispensers be powered from one breaker

to maintain isolated control with the circuit breaker panel in case of problems.

• Units directly driving pumps (suction or submersible) must be supplied power from a

separate breaker. A tag on the motor identifies the maximum current draw of the motor. If
two pumps are supplied from one breaker, that breaker must be capable of handling the
load of both motors.

• DEF units contain a special heater to prevent the DEF fluid from freezing during very cold

weather. Properly size circuit breakers to handle normal pump/dispenser power
requirement plus that for the heater.

In cases where multiple remote dispensers supply power to a single submersible
pump, all breakers controlling the remote dispenser must be on the same phase of
power. Failure to do this will damage the equipment. Provisions must be made to
break both legs of any AC circuit.

CAUTION

STP Control Relay Boxes for Dispensers

• Install a separate control relay for each STP.
• Do not use the dispenser relay to power the STP.
• Combined STP Control Relay/Isolation Relay boxes are recommended.