Equipment and Materials Required at Site
Site Preparation
Equipment and Materials Required at Site
Use of incompatible materials or components with alternative fuels such as E85 can result
in leaks or unexpected failures of components resulting in fire, explosion, or environmental
damage.
When dispensing alternative fuels such as E85, verify with the manufacturer if the material
of all plumping components are compatible with fuels such as E85 being dispensed.
WARNING
• Fuel storage tanks
• STPs and leak detectors for dispensers
• Piping and fittings
• Pit boxes (also known as dispenser sumps)
• Shear valves for dispensers
• Check valves for pumps
• Conduit and gas/oil resistant wiring
• STP control relay boxes for dispensers
• Circuit breakers
• Isolation relays for electronic dispensers
• Emergency power cutoff switch
• Safety warning signs
Place warning signs (for example, No Smoking, Turn Off Engine) where fuel customers
will notice and read them. For warning signs, contact your local distributor.
• Conduit Seal (Potting) Compound (as required by seal manufacturer)
• For aboveground tanks with self-contained pumps, use vacuum-actuated
pressure-regulating valve with a shear section at the pump (Gasboy 52 valve)
• Distribution box(es) or service module(s) is required per unit type
• UL-approved sealant suitable for the application involved
• Wiring and conduit materials as outlined in the wiring diagram suitable for the fluid and
application involved
CAUTION
Applicable to Dispensers Rated for E85 Use:
Do not use tape at the very end of the pipe nipple to avoid tape entering the
dispenser hydraulics. Tape in the hydraulics can cause failures of valves, nozzles,
or other significant problems.
Use only UL-listed TPS PTFE Pipe Sealant manufactured by SAF-T-LOC
International Corp.
Use only UL-listed Taega Technologies Inc. Teflon
®
tape.
Note: Teflon tape must be used only at the inlet pipe connection.