MDE-4333E Atlas Fuel Systems Site Preparation Manual · November 2011

Page 23

Electrical Requirements

Site Preparation

Heater Load Table

Load Table Reference Locations - DEF Dispensers (Cold Weather Units
Only)

A separate breaker is required for the heater (8.5 A @ 120 VAC 60 Hz). For more information,
refer to FE-356 Atlas Retail/Commercial Dispenser Field Wiring.

Note: Heaters are thermostatically controlled and will cycle between on and off during cold

weather to maintain a minimum cabinet temperature.

Sealing ‘Y’ Fittings

‘Y’ seals are installed in conduit runs to minimize passage of vapors, gases, or flames from
one portion of the electrical installation to another through the conduit. Fittings must be
installed in accordance with Articles 501-5 and 502-5 of the National Electric Code and fitting
manufacturers’ instructions.

DEF is non-flammable and creates no explosive vapors. Therefore, installation requirements
for DEF units differ from units that handle hazardous fuels. However, electrical safety
requirements are applicable. If a DEF unit is installed in the Class 1 Division 2 hazard zone of
a pump/dispenser delivering flammable fluids, consult Gasboy Technical Support to determine
requirements for installing DEF units in that area. Generally the unit must be installed to
comply with requirements for units handling flammable fluids for the area within the hazard
zone.

Gasboy uses Killark

Type EY fittings and recommends them or their equivalent for vertical

conduit runs. The following sealing directions are for Killark fittings only and instructions
may vary for other manufacturer’s fittings. Read through all instructions completely before
beginning.

Figure 3-3: Sealing ‘Y’ Fittings

Conduit

Wires

Close-up plug

Sealing compound

Fill to bottom of
threads

Floor dam

Conduit