beautypg.com

Gasboy Atlas Fuel Systems Site Prep Manual User Manual

Page 36

background image

For the 9862 DEF dispenser, you must use the specified shear valve that is rated for
DEF (see

Figure 3-8

on

page 34

).

IMPORTANT INFORMATION

Site Preparation

Plumbing Requirements

Page 32

MDE-4333E Atlas Fuel Systems Site Preparation Manual · November 2011

A shear valve is a NFPA 30A required safety device. It closes automatically to stop product
flow during a fire or if the dispenser gets knocked off the island. It also provides a means of
manually closing inlet pipes.

Figure 3-5: Shear Valve

1-1/2-inch NPT Coupling on unit

Installing contractor supplied
black iron piping to coupling,
including union

Shear valve with shear point
installed flush with grade
±0.75-inch.

Follow shear valve manufacturer’s instructions for installation procedures, testing, and other
procedures.

• Install shear valve on each product inlet pipe.

Note: Gasboy strongly recommends using double-poppet shear valves that shut-off flow

from the tank and the dispenser (for example, OPW

®

#10BHMP, or

Exxon

®

- OPW # 10RMSP).

• Also, install a shear valve on master dispenser satellite outlet and at satellite inlet.
• Do not mount the shear valve upside down.
• Ensure that the valve linkage is accessible and has no interference to opening or closing from

other piping, structure, or components.

• Do not anchor shear valves at this time. For anchoring procedures, refer to MDE-4331

Atlas Fuel Systems Installation Manual.
Note: The dispenser product inlet pipes must be aligned with the shear valve. Do not

restrict shear valve linkage with pipes, braces, and so on.

• Test shear valve operation.
• Close shear valve until equipment start-up. Cap outlet pipe. This prevents dirt and other

particles from getting in the dispenser product line. It also prevents fuel spillage.

• Install a vapor return line where required. This can be done in two ways:

Install a flexible connector or shear section on vapor return pipes as required by

NFPA 30A to ensure the product side shear valves will operate correctly. Use 1-inch pipe
to connect vapor return pipes located inside pump/dispenser.

~ OR ~

Install 1-inch shear valve listed for use with vapor recovery lines. For Vapor Recovery
(Return) Lines, refer to MDE-4331 Atlas Fuel Systems Installation Manual.