beautypg.com

Opw shear valve for 9862kxtw1 def unit, Pit box mounting, Safety signs – Gasboy Atlas Fuel Systems Site Prep Manual User Manual

Page 38

background image

Site Preparation

Plumbing Requirements

Page 34

MDE-4333E Atlas Fuel Systems Site Preparation Manual · November 2011

OPW Shear Valve for 9862KXTW1 DEF Unit

Note: For more information on configuring the shear valve, refer to the manufacturer’s

recommendations.

Figure 3-8: OPW Shear Valve for 9862KXTW1 DEF Unit

4.44

1.22

2.66

1.11” BSPP

Body

Washer-Large

Washer-Small

Spring

Snap Ring

Guide

Stem

Viton Disc

(i)

(ii)

TFR-ISO Reference View

Pit Box Mounting

• Use strongly designed pit boxes that will not twist, bend, or dislocate the shear valve

during a collision.

• Use a pit box which will allow proper access to components during service, does not

expose the pit after unit mounting and properly fastens and supports the unit.

• Anchor pit boxes per pit box manufacturer’s recommendations. Use recommended

fasteners and tighten to manufacturer’s instructions.

• Pit boxes with rain lips are recommended. Otherwise, sealing at the base of the unit may

be required.

• The 9862 DEF unit requires four mounting points, one in each corner.

Safety Signs

• Safety signs warning of potential hazards may be required depending on state and local

codes, and NFPA regulations.

• Gasboy requires installing applicable signs in locations likely to be noticed and read by

users of the equipment.

• Signs must be easily read, bilingual, durable, and fade resistant. Unless local regulations

dictate otherwise, nationally recognized safety symbols with brief text are recommended.

• Signs must include, but are not limited to the following:

Use approved containers

Turn vehicles off during fueling

Static electricity hazards during fueling

Health-related warnings (involving fuels), advisement of fuel

flammability/explosiveness, and others, as required or desirable

No smoking/match warnings

Emergency procedures