13 Frequently Asked Questions
Q: I set the Final Value Cutoff Low at 5 percent. How will the positioner operate?
A:	Assume	that	the	present	command	signal	is	at	50	percent.	If	the	command	signal	is	decreased,	
the	positioner	will	follow	the	command	until	it	reaches	5	percent.	At	5	percent,	the	spool	will	be	
driven	fully	open	or	fully	closed,	depending	on	the	air	action	of	the	valve,	in	order	to	provide	full	
actuator	saturation	and	tight	shutoff.	The	positioner	will	maintain	full	saturation	below	5	percent	
command	signal.	As	the	command	increases,	the	positioner	will	remain	saturated	until	the	command	
reaches	6	percent	(there	is	a	1	percent	hysteresis	value	added	by	the	positioner).	At	this	point,	the	
stem	position	will	follow	the	command	signal.	While	in	Final	Value	Cutoff,	the	Logix	3400IQ LEDs	will	
blink	GGGY.
Q: I have Final Value Cutoff set to 3 percent but the valve will not go below 10 percent.
A:	Is	a	lower	soft	stop	enabled?	The	lower	soft	stop	must	be	less	than	or	equal	to	zero	percent	in	
order	for	the	Final	Value	Cutoff	to	become	active.	If	a	positive	lower	soft	stop	is	written,	this	stop	will	
take	priority	over	the	Final	Value	Cutoff	feature.	When	the	lower	soft	stop	is	reached,	the	positioner	
will	blink	a	GYYR	code.
Q: Will soft stops prevent the valve from going to its fail position?
A:	No.
Q: What is the difference between a model with Standard diagnostics and a model with Advanced
diagnostics?
A:	The	model	with	Advanced	diagnostics	adds	top	and	bottom	actuator	pressure	sensors.	This	
allows	for	more	diagnostic	calculations	such	as	loss	of	pressure,	friction,	advanced	signatures,	and	
troubleshooting.	The	pressure	sensors,	if	present,	are	also	used	in	the	positioner	control	algorithm	to	
enhance	valve	stability.
Q: Can I upgrade from a Standard to an Advanced?
A:	Yes.	Referencing	the	IOM,	an	advanced	pressure	sensor	board	assembly	can	be	purchased.	
Simply	replace	the	pressure	sensor	plug	plate	with	the	advanced	pressure	sensor	board.	Perform	an	
actuator	pressure	calibration.