4 description of cal dip switch settings, 5 re-cal operation – Flowserve 3400IQ Digital Positioner User Manual
Page 26

Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
6
High-Friction Valves Placing	the	switch	to	the	right	optimizes	the	response	for	valves	and	actua-
tors	with	high	friction	levels.	This	setting	slightly	slows	the	response	and	will	normally	stop	limit	
cycling	that	can	occur	on	high-friction	valves.
7.4
Description of Cal DIP Switch Settings
The	sixth	DIP	switch	selects	between	two	calibration	options.	The	function	of	the	Cal	DIP	switch	is	
described	below.
NOTE: The unit must be in OOS mode before a calibration sequence can begin.
Auto Select	Auto	if	the	valve/actuator	assembly	has	an	internal	stop	in	the	open	position.	In	Auto	
mode	the	positioner	will	fully	close	the	valve	and	register	the	0%	position	and	then	open	the	valve	to	
the	stop	to	register	the	100%	position	when	performing	a	self-calibration.	See	detailed	instructions	in	
the	next	section	on	how	to	perform	an	auto	positioner	calibration.
Jog Select	Jog	if	the	valve/actuator	assembly	has	no	physical	calibration	stop	in	the	open	position.	
In	the	Jog	mode	the	positioner	will	fully	close	the	valve	for	the	0%	position	and	then	wait	for	the	user	
to	set	the	open	position	using	the	Jog	buttons	labeled	with	the	up	and	down	arrows.	See	the	detailed	
instructions	in	Section	7.6	on	how	to	perform	a	manual	calibration	using	the	Jog	buttons.
c
WARNING:	During	the	RE-CAL	operation	the	valve	may	stroke	unexpectedly.	Notify	
proper	personnel	that	the	valve	will	stroke,	and	make	sure	the	valve	is	properly	
isolated.
7.5
RE-CAL Operation
NOTE: The unit must be in OOS mode before a calibration sequence can begin.
The	RE-CAL	button	is	used	to	locally	initiate	a	calibration	of	the	positioner.	Pressing	and	holding	the	
RE-CAL	button	for	approximately	three	seconds	will	initiate	the	calibration.	If	the	Config-Switches	
option	is	enabled,	the	settings	of	all	the	configuration	switches	are	read	and	the	operation	of	the	
positioner	adjusted	accordingly.	A	RE-CAL	can	be	aborted	at	any	time	by	briefly	pressing	the	RE-CAL	
button	and	the	previous	settings	will	be	retained.
If	the	Quick	Calibration	switch	(be	careful	not	to	confuse	this	with	the	RE-CAL	button)	is	set	to	
Auto	and	the	valve/actuator	assembly	has	the	necessary	internal	stops	the	calibration	will	complete	
automatically.	While	the	calibration	is	in	progress	you	will	notice	a	series	of	different	lights	flashing	
indicating	the	calibration	progress.	When	the	lights	return	to	a	sequence	that	starts	with	a	green	light	
the	calibration	is	complete.	An	explanation	of	the	various	light	sequences	follows.	The	initial	calibra-
tion	of	extremely	large	or	small	actuators	may	require	several	calibration	attempts.	The	positioner	
adapts	to	the	actuator	performance	and	begins	each	calibration	where	the	last	attempt	ended.	On	an	
initial	installation	it	is	recommended	that	after	the	first	successful	calibration	that	one	more	calibra-
tion	be	completed	for	optimum	performance.