2 mounting to standard valtek rotary valves, See figure 4) – Flowserve 3400IQ Digital Positioner User Manual
Page 15

1
Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
flowserve.com
5.2
Mounting to Standard Valtek Rotary Valves
(See Figure 4)
Figure 4: Standard Rotary Mounting
Positioner Bolts ¼-20 (4)*
* Located in appropriate
hole pattern as indicated on
bracket. (25, 50, 100/200)
Take-off Arm, Rotary 
Lock Washer (2) 
10-32 Bolt 
10-32 Nut 
Self-tapping Screws (2)
Spline Lever Adapter
10-32 Nut 
Lock Washer 
Follower Arm
Logix 3400IQ
Digital Positioner
Bracket Bolts
-18 (2, not shown)
5
/
16
The	standard	rotary	mounting	applies	to	Valtek	valve/actuator	assemblies	that	do	not	have	mounted	
volume	tanks	or	handwheels.	The	standard	mounting	uses	a	linkage	directly	coupled	to	the	valve	
shaft.	This	linkage	has	been	designed	to	allow	for	minimal	misalignment	between	the	positioner	and	
the	actuator.	The	tools	required	for	the	following	procedure	are:
•
5
⁄
32
" Allen wrench
• 1/2" open-end wrench
•
7
⁄
16
" open-end wrench
•
3
⁄
8
" socket with extension
•
3
⁄
16
" nutdriver
1. Fasten the spline lever adapter to the splined lever using two 6 x 1/2" self-tapping screws.
2. Slide the take-off arm assembly onto the spline lever adapter shaft. Insert the screw with star
washer	through	the	take-off	arm	and	add	the	second	star	washer	and	nut.	Tighten	nut	with	
socket	so	arm	is	lightly	snug	on	the	shaft	but	still	able	to	rotate.	This	will	be	tightened	after	
linkage	is	correctly	oriented.
3. Attach follower arm to positioner feedback shaft using the star washer and 10-32 nut.