10 stroke length – Flowserve 3400IQ Digital Positioner User Manual
Page 37

3
Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
flowserve.com
7.14.10 Stroke Length
Stroke	length	is	used	by	the	travel	accumulator.	When	the	stroke	length	and	units	are	set,	the	length	
is	used	to	determine	the	total	travel	accumulated.	The	travel	accumulator	will	have	the	units	associ-
ated	with	stroke.	
ExAMPLE:	Stroke	length	is	set	to	four	inches.	If	the	valve	is	moved	from	0	percent	to	100	percent,	
four	inches	will	be	added	to	the	travel	accumulator.	The	travel	accumulator	units	will	be	inches.	If	
Stroke	length	is	90	degrees	for	a	rotary,	the	travel	accumulator	will	now	have	units	of	degree.	A	0	
percent	to	100	percent	stroke	will	add	90	to	the	travel	accumulator.
NOTE: Stroke length is for information only and is not used during calibration.
Table IX: Transducer Block Characterization Parameters
Parameter
Description
Value - Meaning
Comments
MODE_BLK
The operating mode
of the transducer
block
Auto - Auto (target mode) The transducer
block must be out
of service before
characterization
can be edited or
changed
OOS - Out of Service
CONTROL_
FLAGS
Byte values which
select positioner
operation features
1 - Quick Opening Curve* Loads factory-
defined QO curve as
custom curve.
2 - Equal Percent Curve*
Loads factory-
defined equal
percent curve as
custom curve.
3 - Actuator Type
4 - Advanced Model
5 - Rotary Actuator Gain
6 - Custom
Characterization Active
Activates custom
curve. If Off,
response is Linear.
7 - Fail Position TBD
8 - Air Action
CURVEX
Numeric X value
array for custom
point. (1 x 21 array
points)
X-axis value for custom
stroke characterization
point. Range –10 to 110
Pair each X-value
with corresponding
Y-value to define
the desired point.
Values must be
in ascending (or
equal) order.
CURVEY
Numeric Y value
array for custom
point. (1 x 21 array
points)
Y-axis value for custom
stroke characterization
point. Range –10 to 110
*NOTE: Must not be selected if a custom curve is to be created or edited.
