Flowserve 3400IQ Digital Positioner User Manual
Page 52

Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
c
WARNING:	Spool	(extending	from	the	driver	module	assembly)	is	easily	damaged.	
Use	extreme	caution	when	handling	spool	and	spool	valve	block.	Do	not	handle	the	
spool	by	the	machined	portions	of	spool.	The	tolerances	between	the	block	and	spool	
are	extremely	tight.	Contamination	in	the	block	or	on	the	spool	may	cause	the	spool	to	
hang.
Figure 15: Driver Module Barbed Fitting
#BSCFE'JUUJOH
'MBUPO
)PVTJOH
'MBUPO
%SJWFS
.PEVMF
%SJWFS.PEVMF$PWFS
6. Remove the spool valve block by removing the two Phillips-head screws and carefully sliding
the block off the spool (Figure 14).
7. Carefully remove the spool by sliding the end of the spool out of the connection clip. Excessive
force may bend spool.
8. Remove the main cover.
9. Remove the plastic board cover by removing the three retaining screws (see Figure 16).
10. Disconnect the flexible tubing from the barbed fitting at the driver module assembly (see Figure
15).
11. Use the 1/4" nutdriver to remove the barbed fitting from the driver module assembly.
12. Unplug the two wiring connections that link the driver module assembly to the main PCB
assembly.
13. Feed the two wires on the driver module back into the driver module compartment so that they
stick	out	the	driver	module	opening	(see	Figure	12).	This	will	allow	the	driver	module	to	thread	
out	without	tangling	or	cutting	the	wires.
14. Grasp the base of the driver module and turn it counterclockwise to remove. After it is threaded
out, carefully retract the driver module from the housing.