Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
64
12. Reconnect the field wiring to the user interface board terminals.
13. Install the main PCB into the housing. Insert the retaining screw through the board into the
threaded boss and tighten evenly, using a Phillips screwdriver. Do not overtighten.
14. Install the plastic board cover. Insert the three retaining screws through the plastic cover into the
threaded	boss	and	tighten	evenly,	using	a	Phillips	screwdriver.	Do	not	overtighten	(see	Figure	
16).
15. Reinstall the UI wire connection (see Figure 12).
16. Reinstall all covers.
9
Optional Vented Design
NOTE: See Figures 19 and 20
A standard Logix 3400IQ
positioner is vented directly to the atmosphere. When supply air is
substituted	with	sweet	natural	gas,	piping	must	be	used	to	route	the	exhausted	natural	gas	to	a	safe	
environment.	This	piping	system	may	cause	some	positioner	back	pressure	in	the	main	chamber	
(from	the	modulator	and	regulator)	and	spool	chamber	(from	the	actuator).	Back	pressure	limitations	
are	described	below.
Two	chambers	must	be	vented	on	the	Logix	3400IQ positioners:	the	main	housing	chamber	and	the	
spool	valve	chamber	(Figures	20	and	21).	The	main	chamber	vent	is	located	on	the	backside	of	the	
positioner	(see	Figure	20).	Vented-design	Logix	3400IQ positioners	are	supplied	from	the	factory	
with	a	fitting	installed	in	the	main	chamber	vent.	Connect	the	necessary	tubing/piping	to	this	fitting	to	
route	the	exhausted	natural	gas	to	a	safe	environment.
The	maximum	allowable	back	pressure	from	the	collection	device	on	the	main	housing	vent	is	2.0	
psig	(0.14	barg).	Vent	flow	rate	is	0.5	std	ft
3
/min (1.4 std liter/min).
c
WARNING:	The	back	pressure	in	the	main	housing	must	never	rise	above	2.0	psig	(0.14	
barg).