3 detailed sequence of positioner operations – Flowserve 3400IQ Digital Positioner User Manual
Page 12

Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
1
position	the	stem,	after	any	characterization	or	user	limits	have	been	evaluated,	is	called	the	Control 
Command.	
The Logix 3400IQ
uses a two-stage, stem-positioning algorithm. The two stages consist of an
inner-loop,	spool	control	and	an	outer-loop,	stem	position	control.	Referring	again	to	Figure	1,	a	
stem	position	sensor	provides	a	measurement	of	the	stem	movement.	The	Control Command	is	
compared	against	the	Stem Position.	If	any	deviation	exists,	the	control	algorithm	sends	a	signal	to	
the	inner-loop	control	to	move	the	spool	up	or	down,	depending	upon	the	deviation.	The	inner-loop	
then	quickly	adjusts	the	spool	position.	The	actuator	pressures	change	and	the	stem	begins	to	
move.	The	stem	movement	reduces	the	deviation	between	Control Command	and	Stem Position.	
This	process	continues	until	the	deviation	goes	to	zero.
The	inner-loop	controls	the	position	of	the	spool	valve	by	means	of	a	driver	module.	The	driver	
module	consists	of	a	temperature-compensated	hall	effect	sensor	and	a	piezo	valve	pressure	
modulator.	The	piezo	valve	pressure	modulator	controls	the	air	pressure	under	a	diaphragm	by	
means	of	a	piezo	beam	bender.	The	piezo	beam	deflects	in	response	to	an	applied	voltage	from	the	
inner-loop	electronics.	As	the	voltage	to	the	piezo	valve	increases,	the	piezo	beam	bends,	closing	off	
against	a	nozzle	causing	the	pressure	under	the	diaphragm	to	increase.	As	the	pressure	under	the	
diaphragm	increases	or	decreases,	the	spool	valve	moves	up	or	down	respectively.	The	hall	effect	
sensor	transmits	the	position	of	the	spool	back	to	the	inner-loop	electronics	for	control	purposes.
4.3
Detailed Sequence of Positioner Operations
A more detailed example explains the control function. Assume the unit is configured as follows:
• Unit is in
OOS.
•	 Custom	characterization	is	disabled	(therefore	characterization	is	Linear).
•	 No	soft	limits	enabled.	No	Final	Value	Cutoff	set.
• Valve has zero deviation with a present input command of 50.
• Write to Final_Value to change command.
• Actuator is tubed and positioner is configured air-to-open.
Given	these	conditions,	50	represents	a	Command source	of	50	percent.	Custom characterization	
is	disabled	so	the	Command source	is	passed	1:1	to	the	Control Command.	Since	zero	deviation	
exists,	the	Stem	Position	is	also	at	50	percent.	With	the	stem	at	the	desired	position,	the	spool	valve	
will	be	at	a	middle	position	that	balances	the	pressures	above	and	below	the	piston	in	the	actuator.	
This	is	commonly	called	the	null	or	balanced	spool	position.
Assume the input signal changes from 50 to 75. The positioner sees this as a
Command source
of	75	percent.	With	Linear characterization,	the	Control Command	becomes	75	percent.	Deviation	
is	the	difference	between	Control Command	and	Stem Position :	Deviation	=	75%	-	50%	=	+25%,	
where	50	percent	is	the	present	stem	position.	With	this	positive	deviation,	the	control	algorithm	
sends	a	signal	to	move	the	spool	up	from	its	present	position.	As	the	spool	moves	up,	the	supply	air	
is	applied	to	the	bottom	of	the	actuator	and	air	is	exhausted	from	the	top	of	the	actuator.	This	new	
pressure	differential	causes	the	stem	to	start	moving	towards	the	desired	position	of	75	percent.	As	
