15 characterization retention, 1 initiating a valve signature, 2 system preparation – Flowserve 3400IQ Digital Positioner User Manual
Page 38: 3 signature procedure

Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
3
7.15 Characterization Retention
Once	a	custom	curve	has	been	loaded	into	the	Logix	3400IQ	digital	positioner’s	memory	it	is	retained	
in	the	EPROM	until	it	is	either	edited	or	replaced.	Turning	Custom	Characterization	Active	on	or	off	
now	selects	between	a	linear	response	(off),	or	the	new	custom	curve	(on).	If	either	of	the	other	two	
factory	curves	is	selected	it	will	overwrite	the	custom	curve	in	RAM	only.	The	custom	user-defined	
curve	will	automatically	be	activated	again	when	the	factory	curve	is	deselected.
7.15.1 Initiating a Valve Signature
A	feature	of	the	Logix	3400	positioner	is	the	ability	to	capture	and	store	a	valve	diagnostic	signature.	
A	signature	is	the	collected	data	response	of	the	valve	to	a	predefined	set	of	operating	conditions.	
This	stored	data	can	later	be	uploaded	to	the	host	system	for	analysis	of	potential	problems.	By	
comparing	a	baseline	signature,	when	the	valve	is	new,	to	subsequent	signatures	at	later	times,	a	rate	
of	change	can	be	tracked	which	can	help	predict	possible	faults	in	the	valve	before	they	happen.	This	
is	called	‘predictive	maintenance’.	It	is	important	to	note	that	the	purpose	of	the	positioner	is	to	act	as	
the	data	acquisition	device	for	the	signature.	Analysis	of	the	data	is	not	done	on	the	device,	but	in	the	
supervisory	system.
NOTE: Signature data is lost if the positioner is reset or if the power is cycled
7.15.2 System Preparation
c
WARNING:	By	definition,	the	collection	of	the	signature	requires	the	unmanaged	opera-
tion	of	the	positioner.	Therefore,	the	process	must	be	in	a	safe	operating	mode	where	
unexpected	movement	of	the	valve	will	not	cause	a	hazardous	condition.
Before a valve signature can be run, the Transducer Block must Out-of-Service (OOS).
7.15.3 Signature Procedure
The following steps are an example of how to initiate a ramp signature capture.
1. Make sure the process is in safe condition and notify the control room that the valve will
temporarily be taken off-line.
2. Verify preparedness to proceed.
3. Put the Transducer block MODE_BLK OOS
4. Set SIG_START to desired value.
5. Set SIG_STOP to desired value.
6. Set SAMPLE_TIME to desired value (typically 0.3).
7. In SIG_FLAGS, select; STEP_RAMP, PRESS_MEAS.
8. Write values to the Logix 3400IQ digital positioner.