16 step signature, 17 glossary, 1 collection of stored signature – Flowserve 3400IQ Digital Positioner User Manual
Page 39

3
Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
flowserve.com
9. Set RAMP_RATE to desired value (typically 100).
10. Write value to the Logix 3400IQ digital positioner.
11. In SIG_FLAGS, select BEGIN_SIG.
12. Write value to the Logix 3400IQ digital positioner.
13. The valve will stroke to the beginning position, as defined by SIG_START and will begin ramping
to the desired ending position, as defined by SIG_STOP.
Notice	that	SIG_COUNTER	will	increment	while	this	takes	place.	(Typically	approximately	670	
data	sets	will	be	collected	with	the	above	settings	and	full	stroke	of	the	valve.	Exact	numbers	will	
vary.)
14. SIG_FLAGS indicates SIG COMPLETE.
15. Return the MODE_BLK to auto.
16. Notify control room the valve is back on-line. The stored signature will remain in the Logix
3400IQ	digital	positioner	RAM	until	the	either	the	unit	is	powered	down,	or	another	signature	is	
taken	which	overwrites	the	previous	one.
7.16 Step Signature
If	a	step	signature	was	desired,	simply	do	not	select	STEP_RAMP	in	SIG_FLAGS,	and	then	set	the	
STEP_TIME	prior	to	selecting	BEGIN_SIG.
7.16.1 Collection of Stored Signature
The	collection	of	the	stored	signature	is	accomplished	by	the	host	system.	It	is	not	part	of	the	device.	
See	host	system	programming.	A	simple	utility	using	National	Instruments	NI-FBUS	is	available	from	
Flowserve	for	retrieving	a	signature	file.
The	retrieved	file	is	stored	in	a	text	format	that	can	be	imported	into	other	programs	for	plotting	and	
analysis.	Contact	Flowserve	for	more	details.
7.17 Glossary
A/D Also	called	ADC.	Analog-to-digital	converter.	An	A/D	converts	an	analog	signal	into	an	integer	
count.	This	integer	count	is	then	used	by	the	microcontroller	to	process	sensor	information	such	as	
position,	pressure,	and	temperature.
D/A Also	called	DAC.	Digital-to-analog	converter.	A	D/A	converts	an	integer	count	into	an	analog	
output	signal.	The	D/A	is	used	to	take	a	number	from	the	microcontroller	and	command	an	external	
device	such	as	a	pressure	modulator.