6 manual jog calibration operation, 7 local control of valve position, 8 factory reset – Flowserve 3400IQ Digital Positioner User Manual
Page 27

Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06
flowserve.com
c
WARNING:	When	operating	using	RE-CAL	or	local	control,	the	valve	will	not	respond	to	
external	commands.	Notify	proper	personnel	that	the	valve	will	not	respond	to	remote	
command	changes,	and	make	sure	the	valve	is	properly	isolated.
7.6
Manual Jog Calibration Operation
If	the	Quick	Calibration	switch	is	set	to	Jog,	the	calibration	will	initially	close	the	valve	then	cause	
a	small	jump	in	the	valve	position.	The	jog	calibration	process	will	only	allow	the	user	to	manually	
set	the	span;	zero	position	is	automatically	always	set	at	the	seat.	If	an	elevated	zero	is	needed	a	
handheld	or	other	PC-based	configuration	software	is	required.	When	performing	a	jog	calibration,	
the	LEDs	will	flash	in	a	sequence	of	Y-R-R-G	(yellow-red-red-green)	which	indicates	that	the	user	
must	use	the	Jog	buttons	( 	and	 	)	to	manually	position	the	valve	to	the	100%	position.	When	the	
stem	is	properly	positioned	press	both	the	Jog	buttons	( 	and	 	)	simultaneously	again	to	register	
the	100%	position	and	proceed.	No	more	user	actions	are	required	while	the	calibration	process	
is	completed.	When	the	lights	return	to	a	sequence	that	starts	with	a	green	light	the	calibration	is	
complete.	An	explanation	of	the	various	light	sequences	follows.
7.7
Local Control of Valve Position
Local	control	of	valve	position	can	be	achieved	from	the	user	interface	by	holding	down	both	Jog	
buttons	and	the	RE-CAL	button	simultaneously	for	three	seconds.	While	in	this	mode	the	LEDs	will	
flash	a	YGRR	(yellow-green-red-red)	sequence.	Use	the	two	Jog	buttons	( 	and	 	)	to	manually	
control	the	position	of	the	valve.	To	exit	the	local	control	mode	and	return	to	normal	operation,	briefly	
press	the	RE-CAL	button.
7.8
Factory Reset
To	perform	a	factory	reset,	disconnect	power,	hold	the	RE-CAL	button	down,	and	reconnect	power.	
Performing	a	factory	reset	will	cause	all	of	the	internal	variables,	including	calibration,	to	be	reset	
to	factory	defaults.	The	positioner	must	be	recalibrated	after	a	factory	reset.	User	configured	limits,	
alarm	settings,	and	valve	information	will	also	need	to	be	restored.
c
WARNING:	Performing	a	factory	reset	may	result	in	the	inability	to	operate	the	valve	until	
reconfigured	properly.	Notify	proper	personnel	that	the	valve	may	stroke,	and	make	sure	the	
valve	is	properly	isolated.
7.9
Logix 3400IQ Status Condition
The	blink	codes	used	to	convey	the	status	of	the	Logix	3400IQ digital	positioner	are	described	in	the	
table	below.	In	general,	any	sequence	starting	with	a	green	light	flashing	first	is	a	normal	operating	
mode	and	indicates	that	there	are	no	internal	problems.	Any	sequence	starting	with	a	yellow	light	
flashing	indicates	that	the	unit	is	in	a	special	calibration	or	test	mode,	or	that	there	was	a	calibra-