tion problem. Any sequence starting with a red light flashing indicates that there is an operational
problem with the unit.
Table VII: Status and Conditions
Co
lo
rs
Id
en
tifi
er
Indication and Resolution
G - - -
Any sequence starting with a green light flashing first is a normal operating mode and
indicates that there are no internal problems.
GGGG
1
Normal operation No errors, alerts, or warnings.
GGGY
2
Final Value cutoff active The command is below or above the user-set limits for tight
shutoff feature. This is a normal condition for a closed valve. The factory default setting is 1%
and 110% command. To clear the condition use handheld or Host software to reset the tight
shutoff if the range is incorrect or adjust the command signal above the specified Final Value
cutoff.
GGYR
4
Initializing This sequence should only be visible for three sequences when powering up
the unit.
GGRG
5
Cycle limit exceeded (user-set) The cycle limit set by the user has been exceeded. To clear
use handheld or Host software to reset.
GGRY
6
Travel limit exceeded (user-set) The total accumulated travel limit set by the user has been
exceeded. To clear use handheld or Host software to reset.
GYYR
7
Soft Stop Low (user-set) The unit is being commanded to exceed a user-defined lower
position limit and the internal software is holding the position at the limit. The function is
similar to a mechanical limit stop except it is not active if the unit is un-powered. To clear the
condition use handheld or Host software to reset the limit if more travel is needed or adjust
the command signal back in the specified range.
GYRY
8
Soft Stop High (user-set) The unit is being commanded to exceed a user-defined upper
position limit and the internal software is holding the position at the limit. The function is
similar to a mechanical limit stop except it is not active if the unit is un-powered. To clear the
condition use handheld or Host software to reset the limit if more travel is needed or adjust
the command signal back in the specified range.
GRYR
9
Posalert Low (user-set) The position has reached or is exceeding a user-defined lower
position indicator similar to a limit switch indicator. To clear the condition use handheld or
Host software to reset the indicator if more travel is needed or adjust the command signal
back in the specified range.
GRRY
10
Posalert High (user-set) The position has reached or is exceeding a user-defined upper
position indicator similar to a limit switch indicator. To clear the condition use handheld or
Host software to reset the indicator if more travel is needed or adjust the command signal
back in the specified range.
Y - - -
Any sequence starting with a yellow light indicates that the unit is in a special calibration
or test mode, or that there was a calibration problem.
YGYG
11
Signature test in progress This is a test initiated by Host software that can only be
cancelled by that software.
YRGG
13
Stroke calibration in progress Calibration sequence started either using the local RE-CAL
button or by a handheld or Host software. It may be cancelled by briefly pushing the RE-CAL
button.
Continued on page 29