7.14 Alerts
7.14.1 FINAL_VALUE_CUTOFF
The	FINAL_VALUE_CUTOFF	or	tight	shutoff	feature	of	the	Logix	3400IQ	digital	positioner	allows	the	
user	to	control	the	level	at	which	the	command	signal	causes	full	actuator	saturation	in	the	closed	or	
open	position.
This	feature	can	be	used	to	guarantee	actuator	saturation	in	the	closed	or	open	position	or	prevent	
throttling	around	the	seat	at	small	command	signal	levels.	To	enable,	use	configuration	to	apply	the	
desired	FINAL_VALUE_CUTOFF	threshold.
NOTE:	The	positioner	automatically	adds	a	1	percent	hysteresis	value	to	the	FINAL_VALUE_CUTOFF_
LO	setting	to	prevent	jumping	in	and	out	of	saturation	when	the	command	is	close	to	the	setting.
7.14.2 Effects of FINAL_VALUE_CUTOFF on Operation
With	the	FINAL_VALUE_CUTOFF_LO	set	at	5	percent	the	positioner	will	operate	as	follows:	Assume	
that	the	present	command	signal	is	at	50	percent.	If	the	command	signal	is	decreased,	the	positioner	
will	follow	the	command	until	it	reaches	5	percent.
At	5	percent,	full	actuator	saturation	will	occur.	The	actuator	will	maintain	full	saturation	below	5	
percent	command	signal.	Now,	as	the	command	increases,	the	positioner	will	remain	saturated	until	
the	command	reaches	6	percent	(remember	the	1	percent	hysteresis	value	added	by	the	positioner).	
At	this	point,	the	stem	position	will	follow	the	command	signal.
If	the	FINAL_VALUE_CUTOFF_LO	is	set	to	3	percent	but	the	valve	will	not	go	below	10	percent,	
SOFTSTOP_LOW	may	be	enabled.	The	lower	soft	limit	must	be	less	than	or	equal	to	0	percent	in	
order	for	the	FINAL_VALUE_CUTOFF_LO	to	become	active.
If	soft	stops	are	active	(ie:	SOFTSTOP_LOW	=	0	or	SOFTSTOP_HIGH	=	100)	FINAL_VALUE_CUTOFF	
is	disabled.	
7.14.3 Soft Limits
Unlike	position	alerts,	soft	limits	prevent	the	stem	position	from	going	below	or	above	the	configured	
limits.	If	the	command	signal	is	trying	to	drive	the	position	past	one	of	the	limits,	the	yellow	LED	will	
blink	but	the	stem	position	will	remain	at	the	set	limit.
7.14.4 Travel Accumulator
The	travel	accumulator	is	equivalent	to	a	car	odometer	and	sums	the	total	valve	movement.	Using	the	
user	defined	stroke	length	and	travel	dead-band,	the	Logix	3400IQ	digital	positioner	keeps	a	running	
total	of	valve	movement.	When	the	positioner	first	powers	up,	high	and	low	dead-band	limits	are	
calculated	around	the	present	position.	When	the	stem	position	exceeds	the	travel	dead-band,	the	
movement	from	the	center	of	the	deadband	region	to	the	new	position	is	calculated	and	added	to	the	
travel	accumulator.	From	this	new	position,	deadband	high	and	low	limits	are	again	calculated.