Comtest Networks MTAS-192 METALLIC TEST ACCESS SYSTEM User Manual

Page 34

background image

Comtest Networks

CT-IG-MTAS192-2008-v1_8.doc

MTAS-192

28

Installation Guide

June 2006

4.2.3 Connecting Line/Facility and POTS/Equipment RJ-21 Connectors


NOTE
: Please see Appendix A for cable pinouts.

Step 1. Connect one end of the CAT3/5 24-pair cable to the "LINE/FACILITY" female

RJ-21 connector on the MTAS backplane. For right-angle RJ-21 connectors,
use a tie wrap to secure the top of connector to the cable tie mount and RJ-21
connector; use a screw for bottom. Please see Figure 27 and Figure 28.

Step 2. Connect the other end to the subscriber MDF.
Step 3. Connect one end of the CAT3/5 24-pair cable to the "POTS/EQUIPMENT"

female RJ-21 connector on the MTAS backplane.

Step 4. Connect the other end to the voice switch.
Step 5. Dress, tie, and label cables following local procedures.
Step 6. Repeat steps #1-5 for all provisioned line cards.

Figure 26: Cabling RJ-21 Connections

Figure 27: Run Tie-wrap through Slot of Cable

Tie Mount

Figure 28: Right Angle RJ-21 Male Connector

Tie-wrapped to Cable Tie Mount

1

2

3

4

"DSL" to DSLAM

"LINE/FACILITY" to

subscriber

MDF

"POTS/EQUIPMENT" to

voice switch