beautypg.com

Comtest Networks MTAS-192 METALLIC TEST ACCESS SYSTEM User Manual

Page 25

background image

CT-IG-MTAS192-2008-v1_8.doc

Comtest Networks

MTAS-192

June 2006

Installation Guide

19

Step 4. When the card will go no further, pull the card ejector tab upwards and push it

towards the shelf in one motion to completely seat the card.

Step 5. When the card is completely seated, lock it in place by pushing and hand-

tightening the slotted card locking screws until they are tight – DO NOT OVER-
TORQUE
.

Step 6. Repeat for all the cards to be installed on the shelf.

NOTE: The MTAS-CM (Master) control card has a block of DIP switches that are set to
a default setting of 0 (0-0-0-0) and factory-sealed with a plastic film. These DIP switches
must remain at 0-0-0-0 (see Figure 18: ). MTAS-CS (Slave) control card DIP switch
settings, however, must be set to identify the shelf's unique address in a daisy-chain of
up to 12 MTAS shelves

Slave shelves require their MTAS-CS cards to be set to a unique number between 1
and 11 in binary, to identify the slave shelf's logical ID in the daisy-chain. See Figure 18:
to locate DIP switches and consult Appendix A for the MTAS Control Card DIP switch
settings table.

In addition to physically inspecting the DIP switch settings, they can also be verified by
viewing the Binary ID LEDs (8, 4, 2, 1) on the slave card faceplate (see
Figure 22).

Figure 18: MTAS-CM (Control Master) DIP Switch Location