3.3.1 Low Input Voltage Range Configuration (107/115 V)

In order to change the voltage range configuration:

1. Turn off the input circuit breaker.

2. Disconnect AC input power by unplugging the power cord.

3. Remove the AC Power Source top cover by removing (17) #6-

32 x 5/16” FLH screws.

There are a total of 7 screws on the sides and 10 screws on the top that hold the cover.

4. The low input voltage range is set by removing the wire from CR1-AC2 and connecting it

to A4-E2.

Figure 3-3: Internal Jumper Location, Input Line Voltage 107/115