beautypg.com

14 surge protector installation, Overview, Installation – D-Link KX-TDA100 User Manual

Page 68

background image

2.2 Installation of the Hybrid IP-PBX

68

Installation Manual

2.2.14 Surge Protector Installation

Overview

A massive electrical surge can be caused if lightning strikes a telephone cable 10 m above ground, or if a
telephone line comes into contact with a power line. A surge protector is a device that is connected to a trunk
to prevent potentially dangerous electrical surges from entering the building via the trunk and damaging the
Hybrid IP-PBX and connected equipment.

To protect the system from electrical surges, we strongly recommend connecting the system to a surge
protector that meets the following specifications:

Surge arrestor type: 3-electrode arrestor

DC spark-over voltage: 230 V

Maximum peak current: at least 10 kA

Additionally, proper earthing is very important for the protection of the system (refer to "2.2.5 Frame Earth
Connection
").

Many countries/areas have regulations requiring surge protection. Be sure to comply with all applicable
laws, regulations, and guidelines.

Installation

CS

Trunk

Trunk

Trunk

Extn.

Extn. Extn.

Extn.: Extension line

Surge

Protector

Terminal

Board

Hybrid

IP-PBX

Frame
Earth

SLT

Earth

PT