2.2 Installation of the Hybrid IP-PBX

44

Installation Manual

2.2.4

Installing/Replacing the Power Supply Unit

Function

Accessory and User-supplied Items

Accessory (included): Screws × 4

User-supplied (not included): earthing wire, Back-up Battery Cable (KX-A228 for PSU-S and PSU-M, or
KX-A229 for PSU-L)

Notes

For details about frame earth connection, refer to "2.2.5 Frame Earth Connection".

For details about backup batteries connection, refer to "2.2.6 Backup Batteries Connection".

Safety Instructions

Each PSU complies with Safety Class 1 of IEC60950, EN60950, UL60950,
CAN/CSA-C22.2 No.60950, and AS/NZS60950; therefore a protective earth connection exists between the
mains outlet ground and the PSU case. To ensure the PBX chassis is safely grounded, it is essential that
the PSU case be securely fastened to the PBX chassis with the 4 screws provided with each PSU.

When installing or replacing PSU, basic safety precautions should always be followed to reduce the risk of
fire, electric shock and injury to persons, including the following:

1.

Never install or replace PSU during a lightning storm.

2.

Never install or replace PSU in wet locations.

PSU Type

Lower/Upper Input Voltage Range

Current

Input Frequency

PSU-S
(for KX-TDA100)

Lower: 100 V AC to 130 V AC

1.4 A

50 Hz or 60 Hz

Upper: 200 V AC to 240 V AC

0.8 A

PSU-M
(for KX-TDA100/200)

Lower: 100 V AC to 130 V AC

2.5 A

Upper: 200 V AC to 240 V AC

1.4 A

PSU-L
(for KX-TDA200)

Lower: 100 V AC to 130 V AC

5.1 A

Upper: 200 V AC to 240 V AC

2.55 A

AC Inlet

Power Switch

AC Inlet

Power Switch

PSU-S

PSU-M/PSU-L

Battery Switch

Earth Terminal

Battery Switch

Earth Terminal

Battery Connector

Battery Connector