GSM-PRO


- 31 -

When there are one or more email addresses in the user list, the email is sent only once to all email
addresses at the beginning of the sequence.

6.3

6.3

6.3

6.3

Analog input

Analog input

Analog input

Analog inputssss

Each analog input (AI) represents a scaled value from 0 to 10V. Within this scale threshold values can
be monitored.


6.3.1

6.3.1

6.3.1

6.3.1

Configuration

Configuration

Configuration

Configuration

Configure the following items:

Name; this name must be unique and cannot be used with any other input or output.

Default set as AI1 to AI8.

The unit for the input feedback. E.g. litres (Ltr) or kilograms (kg).

Log this AI at a pre-set interval, see chapter 5.4 for interval settings.

The min. value represents the scaled value for 0V

The max. value represents the scaled value for 10V

Lower limit threshold

Upper limit threshold

Minimal change (hysteresis)

Send only the user defined text, this sends only the text defined in the message box, no

module name, IO name and timestamp.

The Analog Inputs can generate messages including value and unit when:

-

The upper limit + hysteresis is reached

-

The lower limit – hysteresis is reached

-

The status recovers between the upper and lower limit +/- hysteresis