Electrical specifications
Electrical specifications
Electrical specifications
Electrical specifications
Manual
Manual
Manual
Manual
=
=
=
=
=
=
The CMS-UI-R is a multi-functional 3-way isolated
threshold relay. This module is used for control and
alarm functions.
The 3-way isolation enables the module to be used
locally as well as in the vicinity of the controlling
system.
The inputs and output relay functions of the converter
are configured by means of dipswitches.
Any combination of input and output can be chosen,
so numerous different control functions can be set.
Default input/output relay setting is 0..10V / threshold
with hysteresis.
Other default input/output settings on request.
=
=
Order information
Order information
Order information
Order information
type
CMS-UI-R
cat.no
95120.8
Input data
Input data
Input data
Input data
range (select via dipswitches)
0-1V/0-2V/0-2,5V/0-5V/1-5V/0-10V/0-20V/0-40V/0-5mA/0-10mA/0-20mA/4-20mA
max. input signal (U / I)
40V / 25mA
input resistance (U / I)
> 200 kOhm / 50 Ohm
Output data
Output data
Output data
Output data
relay output
1CO contact, 240V~
output function (select via dipswitch)
threshold with hysteresis / ON and OFF threshold / threshold range control
adjustment range Threshold / Hysteresis
10…90%
rated / inrush current (ohmic load)
3A / 5A
max. power rating
1200VA @ 240V ac, 5A
life span @ 23°C and ohmic load
Electrical: at rated load: > 1,5 x 10
5
cycles.
Mechanical: > 15 x 10
6
cycles
contact material
AgNi
test voltage
4kV
General data
General data
General data
General data
module power supply
24V DC ±25%
module current
Approx. 50mA
temperature coefficient
< 0,02 %/°C
max. conversion frequency
10Hz
CE marking
Low Voltage Directive (LVD) 2006/95/EC, according requirements of EN 61010
EMC Directive 2004/108/EC, according requirements of EN 55011 and EN 61326-1
isolation voltage input / power
1kV, 50Hz, 1min.
isolation voltage input / output
4kV
isolation voltage output / power
4kV
operating / storage temperature
0°C…+55°C / -20°C…+70°C
conductor cross section
0,2 - 2,5 mm²
connection system
screw clamp connection, pluggable
insulation stripping length
7 mm
mounting / installation position
DIN-rail TS35 / any
module size LxWxH (TS35)
17,5 x 99 x 114,5mm
weight
120 gr
=
=
=
Features:
Features:
Features:
Features:
• Multifunctional analog input (0..1V, 0..2V, 0..2,5V, 0..5V, 1..5V, 0..10V, 0..20V,
0..40V, 0..5mA, 0..10mA, 0..20mA, 4..20mA)
• 3 output relay control functions (threshold with hysteresis, ON and OFF threshold,
threshold range control)
• Analog signal range selectable via DIP switches
• 3-Way galvanic isolation
• Power supply 24V DC
• Other analog signal ranges on request
Cms-ui-r manual rev0.fl.doc