CONTA-CLIP CMS-110A-UI User Manual
Conta-electronics
CONTA-ELECTRONICS
=====
=
=
=
=
=
=
=
=
=
CMS
CMS
CMS
CMS----I10A
I10A
I10A
I10A----UI
UI
UI
UI
=
=====
=====
=====
=====IIIIsolated
solated
solated
solated S
S
S
Signal
ignal
ignal
ignal converter
converter
converter
converter
Further information:
www.conta-clip.com
Cat. No.: 95120.0
Further information:
www.conta-clip.com
Electrical specifications
Electrical specifications
Electrical specifications
Electrical specifications
Manual
Manual
Manual
Manual
=
=
=
=
=
=
The CMS-I10A-UI is a multi-functional 3-way isolated
signal converter. This module is used for galvanic
isolated high current measurement and conversion.
Also a threshold relay output is provided.
The 3-way isolation enables the module to be used
locally as well as in the vicinity of the controlling
system.
The inputs and outputs of the converter are configured
by means of dipswitches.
Any combination of input and output can be chosen,
so numerous different signal conversions can be set.
Default input/output setting is 0..10A / 0..10V.
Other default input/output settings on request.
=
=
Order information
Order information
Order information
Order information
Type
CMS-I10A-UI
Cat.no
15901.2
Input data
Input data
Input data
Input data
range (select via dipswitches)
0..0,5A / 0..1A / 0..5A / 0..10A AC and DC
max. voltage
250V AC/DC
measuring principle
true RMS / arithmetic average
AC input frequency
45..65Hz
Output data
Output data
Output data
Output data
voltage output (select via dipswitch)
0..10V / 0..5V / 1..5V / 10..0V
load resistance
> 1kOhm
current output (select via dipswitch)
0..5mA, 0..10mA, 0..20mA, 4..20mA
load resistance
< 600 Ohm
relay output
1 CO contact
max. switching voltage
250V~
rated / inrush current (ohmic load)
3A / 5A
max. power rating
750VA
electrical life span
at rated, 23°C and ohmic load: 3 x 105 cycles
mechanical life span
15 x 106 cycles
contact material
AgNi 90/10
test voltage coil-contact
4kV
General data
General data
General data
General data
module power supply
24V DC ±10%
module current (without load)
Approx. 60mA
conversion error
< 0,5% of In
linearity error
< 0,5% of In
temperature coefficient
< 0,05 %/°C
response time
200ms
offset voltage @ 3x In overload
< 0,7% of In
CE marking
Low Voltage Directive (LVD) 2006/95/EC, according requirements of EN 61010
EMC Directive 2004/108/EC, according requirements of EN 55011 and EN 61326-1
isolation voltage input / power
3,5kV, 50Hz, 1min.
isolation voltage input / output
3,5kV, 50Hz, 1min.
isolation voltage output / power
1kV, 50Hz, 1min.
operating / storage temperature
0°C…+50°C / -20°C…+70°C
conductor cross section
0,2 - 2,5 mm²
connection system
screw clamp connection, pluggable
insulation stripping length
7 mm
mounting / installation position
DIN-rail TS35 / any
module size LxWxH (TS35)
17,5 x 99 x 114,5mm
weight
130 gr
=
=
=
Features:
Features:
Features:
Features:
• Multiple High Current input (0..0,5A, 0..1A, 0..5A, 0..10A, True RMS AC
and AVG DC)
• Multifunctional analog output (U,I)
• Threshold relay output with adjustable set point and hysteresis
• Current range selectable via DIP switches
• 3-Way galvanic isolation
• Power supply 24V DC
• Extremely simple Zero-Calibration by pressing calibration button for 5
seconds
CMS-I10A-UI manual rev1.fl.doc