Status byte, 7operation, 3 status byte – Pilz PSSu E F PS User Manual

Page 38

background image

7.3

Status byte

7

Operation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-4

7.3

Status byte

7300

Status byte

7-

][BA_Betrieb FS Versorgung Statusbyte

The first supply module after the head module can communicate a vari-

ety of status information to the ST-PII (see table below). The information

is transmitted using the module's status byte. Read access (R) is config-

ured for that purpose.

Structure and contents of the status byte

Bit number

Signal

Key

0

0

SafetyBUS p in a STOP condition

1

SafetyBUS p in a RUN condition

1

0

The PSSu section configured for the FS inputs (section A or B) is in a STOP condition.

1

The PSSu section configured for the FS inputs (section A or B) is in a RUN condition.

2

0

The PSSu section configured for the FS outputs (section A) is in a STOP condition.

1

The PSSu section configured for the FS outputs (section A) is in a RUN condition.

3

0

No general error in the PSSu FS section

1

General error in the PSSu FS section

4

0

No general error in the PSSu ST section

1

General error in the PSSu ST section

5

0

No error on the FS modules

1

At least one FS module is registering an error

6

0

No error on the ST modules

1

At least one ST module is registering an error

7

0

Reserved

1