Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-5

6.2

Terminal configuration

6

Wiring

For use as a supply module to refresh the module supply and periph-

ery supply

For use as a supply module to form supply groups

– To interrupt the incoming periphery supply and C-rail

– To provide subsequent modules with the module supply, periphery

supply and C-rail supply

With these base modules the supply module cannot be used as the

first module after the head module.

Base module

Terminal configuration

Screw terminals:
PSSu BS-R 1/8S
PSSu BS-R 1/8S-T

Cage clamp terminals:
PSSu BS-R 1/8C
PSSu BS-R 1/8C-T

11: +24 V infeed for module supply,
interrupted to the left

21: 0 V infeed for module supply

12-22: 0 V periphery supply,
interrupted to the left
(12-22 linked within the base module)

13-23: +24 V periphery supply,
interrupted to the left
(13-23 linked within the base module)

14-24 C-rail supply,
interrupted to the left
(14-24 linked within the base module)

21

11

22

12

23

13

24

14