Messages

7

Operation

7

7000

Operation

Operation

7-

7.1

Messages

7100

Messages

7-

][BA_Betrieb Störung LED "Err" PS

A module error is displayed via the “Err” LED (see section entitled “Dis-

play elements”), signalled to the head module and then entered in the

head module's error stack or diagnostic log.

][BA_Betrieb Fehler FS PS

The module can detect the following errors:

Further information on PSSu error messages is available in the online

help for PSS WIN-PRO or PAS4000.

Module error

Explanation

Remedy

Start-up error

Error as the PSSu system starts up

Change faulty module.

Configuration error

Incorrect module type configured.

The configured hardware registry does
not match the actual hardware regis-
try.

FS communication error

Error during FS communication Change

faulty

module.

Temperature error: too warm

Ambient temperature too high:
Entry in the error stack or diagnostic
log

Ensure there is sufficient ventilation in
the control cabinet or prevent over-
load.

Overvoltage error

A system voltage or infeed is too high. Stabilise the supply or change the

faulty supply voltage module.

Undervoltage error

A system voltage or infeed is too low.

Stabilise the supply or change the
faulty supply voltage module.

Error in the overvoltage protection di-
odes

Overvoltage protection diodes are de-
fective.

Change faulty supply voltage module.