Operation, Messages, 7operation – Pilz PSSu E F PS User Manual
Page 35: 1 messages

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
7-1
7.1
Messages
7
Operation
7
7000
Operation
Operation
7-
7.1
Messages
7100
Messages
7-
][BA_Betrieb Störung LED "Err" PS
A module error is displayed via the “Err” LED (see section entitled “Dis-
play elements”), signalled to the head module and then entered in the
head module's error stack or diagnostic log.
][BA_Betrieb Fehler FS PS
The module can detect the following errors:
Further information on PSSu error messages is available in the online
help for PSS WIN-PRO or PAS4000.
Module error
Explanation
Remedy
Start-up error
Error as the PSSu system starts up
Change faulty module.
Configuration error
Incorrect module type configured.
The configured hardware registry does
not match the actual hardware regis-
try.
FS communication error
Error during FS communication Change
faulty
module.
Temperature error: too warm
Ambient temperature too high:
Entry in the error stack or diagnostic
log
Ensure there is sufficient ventilation in
the control cabinet or prevent over-
load.
Overvoltage error
A system voltage or infeed is too high. Stabilise the supply or change the
faulty supply voltage module.
Undervoltage error
A system voltage or infeed is too low.
Stabilise the supply or change the
faulty supply voltage module.
Error in the overvoltage protection di-
odes
Overvoltage protection diodes are de-
fective.
Change faulty supply voltage module.