Terminal configuration, 6wiring, 2 terminal configuration – Pilz PSSu E F PS User Manual
Page 30

6.2
Terminal configuration
6
Wiring
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-4
6.2
Terminal configuration
6200
Terminal configuration
6-
][Klemmenbelegung PS
For use as a general supply module, supplying a head module and
subsequent modules
Base module
Terminal configuration
Screw terminals:
PSSu BS 1/8S
PSSu BS 1/8S-T
Cage clamp terminals:
PSSu BS 1/8C
PSSu BS 1/8C-T
11: +24 V infeed for module supply
21: 0 V infeed for module supply
12-22: 0 V periphery supply,
interrupted to the left
(12-22 linked within the base module)
13-23: +24 V periphery supply,
interrupted to the left
(13-23 linked within the base module)
14-24 C-rail supply,
interrupted to the left
(14-24 linked within the base module)
21
11
22
12
23
13
24
14
Head Module
I/O Module
I/O Module
I/O Module
I/O Module
Periphery Supply
(24 V DC)
C-rail Supply
Infeed for
Module Supply
(24 V DC)
Module bus
[ . . . ]
PSSu E F PS(-T)
[ . . . ]
I/O Module
5 V DC
24 V DC