beautypg.com

Terminal configuration, 6wiring, 2 terminal configuration – Pilz PSSu E S 4AI U User Manual

Page 42

background image

6.2

Terminal configuration

6

Wiring

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-4

6.2

Terminal configuration

6200

Terminal configuration

6-

][Klemmenbelegung ST-AI 4xU

Base module

Terminal configuration

Screw terminals:
PSSu BP 1/8S
PSSu BP 1/8S-T

Cage clamp terminals:
PSSu BP 1/8C
PSSu BP 1/8C-T

Without C-rail:

11: Input I0

21: Input I1

12-22: 0 V analogue
(12-22 linked within the base module)

13-23: Cable shield
(13-23 linked within the base module)

14: Input I2

24: Input I3

Screw terminals:
PSSu BP 1/12S
PSSu BP 1/12S-T

Cage clamp terminals:
PSSu BP 1/12C
PSSu BP 1/12C-T

Without C-rail:

11: Input I0

21: Input I1

12-22: 0 V analogue
(12-22-15-25 linked within the base
module)

13-23: Cable shield
(13-23-16-26 linked within the base
module)

14: Input I2

24: Input I3

15-25: 0 V analogue
(12-22-15-25 linked within the base
module)

16-26: Cable shield
(13-23-16-26 linked within the base
module)

21

11

22

12

23

13

24

14

21

11

22

12

23

13

24

14

26

16

25

15

This manual is related to the following products: