4.1

Module features

4

Function description

4

4000

Function description

Function description

4-

4.1

Module features

4100

Module features

4-

4.1.1

Functions

Functions

4-

][Funktionsbeschreibung BA Einleitung ST-AI

The module supply provides the module with voltage.

The input signals are read in, analogue prefiltered and converted into

digital signals. The resolution is 12 bits (4095 steps) and is converted

into a 16 Bit value. Additional signal processing can be defined using the

system software (see schematic representation of signal processing).

The individual steps are described in the "Configuration" section.

The input signals are transmitted to the head module via the ST module

bus. As an option the input module can send status information for each

input.

All the configuration data is stored in the head module and is assigned

to the input module on restart. This way the configuration data is re-

tained even if you change the input module.

][Funktionsdiagramm ST-AI ohne Filter

Schematic representation of signal processing:

4.1.2

Integrated protection mechanisms

Integrated protection mechanisms

4-

][Schutzmechanismen E/A-Module

When the PSSu E F PS1(-T) is used to supply the system, the module

supply is buffered for 20 ms if the supply voltage is interrupted.

][Schutzmechanismen ST-Module

The module detects the following errors:

Start-up error

Configuration error

ST communication error

Bus termination error