beautypg.com

Limit values, 4function description, 2 configuration – Pilz PSSu E S 4AI U User Manual

Page 24: 2 limit values

background image

4.2

Configuration

4

Function description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-8

4.2.2

Limit values

Limit values

4-

][Funktionsbeschreibung_BA_Konfig Grenzwert ST-AI allgemein

The module has range monitoring and limit value monitoring on each

channel:

Range monitoring

– Upper limit value: 4095

D

– Lower limit value: -4095

D

– The module compares the upper and lower limit value with the dig-

ital value after the hardware calibration (values with 12 bits plus

sign) and writes the result of the comparison as follows:

– System environment A:

In the status byte (see "PSSu assignment in system environment
A")

– System environment B:

In the I/O data element "Overrange" or "Underrange" (see "PSSu
assignment in system environment B").

– The limit of the measuring range corresponds to 4095

D

.

Limit value monitoring

– Limit value 1

– Limit value 2

– The module compares limit value 1 and limit value 2 with the digital

value after scaling (values with 15 bits plus sign) and writes the re-

sult of the comparison as follows:

– System environment A:

In the status byte (see "PSSu assignment in system environment
A")

– System environment B:

In the I/O data element "LimitValue1" or "LimitValue2" (see
"PSSu assignment in system environment B").

– The limit of the measuring range corresponds to 32 767

D

with de-

fault scaling values.

You can change the default values in the system software.

][Funktionsbeschreibung_BA_Konfig Grenzwert ST-Ein 4xU

This manual is related to the following products: