Limit values, 4function description, 2 configuration – Pilz PSSu E S 4AI U User Manual
Page 24: 2 limit values

4.2
Configuration
4
Function description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-8
4.2.2
Limit values
Limit values
4-
][Funktionsbeschreibung_BA_Konfig Grenzwert ST-AI allgemein
The module has range monitoring and limit value monitoring on each
channel:
Range monitoring
– Upper limit value: 4095
D
– Lower limit value: -4095
D
– The module compares the upper and lower limit value with the dig-
ital value after the hardware calibration (values with 12 bits plus
sign) and writes the result of the comparison as follows:
– System environment A:
In the status byte (see "PSSu assignment in system environment
A")
– System environment B:
In the I/O data element "Overrange" or "Underrange" (see "PSSu
assignment in system environment B").
– The limit of the measuring range corresponds to 4095
D
.
Limit value monitoring
– Limit value 1
– Limit value 2
– The module compares limit value 1 and limit value 2 with the digital
value after scaling (values with 15 bits plus sign) and writes the re-
sult of the comparison as follows:
– System environment A:
In the status byte (see "PSSu assignment in system environment
A")
– System environment B:
In the I/O data element "LimitValue1" or "LimitValue2" (see
"PSSu assignment in system environment B").
– The limit of the measuring range corresponds to 32 767
D
with de-
fault scaling values.
You can change the default values in the system software.
][Funktionsbeschreibung_BA_Konfig Grenzwert ST-Ein 4xU