beautypg.com

Adc raw value and initialisation value, Hardware calibration, Manufacturer scaling – Pilz PSSu E S 4AI U User Manual

Page 20: 4function description, 2 configuration

background image

4.2

Configuration

4

Function description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-4

4.2.1.1

ADC raw value and initialisation value

ADC raw value and initialisation value

4-

][Funktionsbeschreibung_BA_Konfig Skalier ADC

You can configure each channel so that the raw value from the AD con-

verter is issued directly, without calibration or scaling.

If the AD converter fails to supply a valid value, the module will adopt the

ADC initialisation value for this channel instead. The default value is

4096

D

(1000

H

).

4.2.1.2

Hardware calibration

Hardware calibration

4-

][Funktionsbeschreibung_BA_Konfig Skalier HW-Abgleich

Each channel is calibrated ex-works in order to correct component dis-

persion and other influences.

The range is divided so that zero is assigned the value 0 and the end

point is assigned the value 4095

D

(0FFF

H

).

4.2.1.3

Manufacturer scaling

Manufacturer scaling

4-

][Funktionsbeschreibung_BA_Konfig Skalier Herst. Ein

The manufacturer scaling is used to define the offset (zero point com-

pensation) and gain (amplification) of the digital signal.

Manufacturer scaling active (default setting)

Default values for manufacturer scaling:

– Offset (b

1

): 0

– Gain (a

1

): 8194

D

(2002

H

)

INFORMATION

The default setting for gain (a

1

) means an amplification factor of

8.