Adc raw value and initialisation value, Hardware calibration, Manufacturer scaling – Pilz PSSu E S 4AI U User Manual
Page 20: 4function description, 2 configuration

4.2
Configuration
4
Function description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-4
4.2.1.1
ADC raw value and initialisation value
ADC raw value and initialisation value
4-
][Funktionsbeschreibung_BA_Konfig Skalier ADC
You can configure each channel so that the raw value from the AD con-
verter is issued directly, without calibration or scaling.
If the AD converter fails to supply a valid value, the module will adopt the
ADC initialisation value for this channel instead. The default value is
4096
D
(1000
H
).
4.2.1.2
Hardware calibration
Hardware calibration
4-
][Funktionsbeschreibung_BA_Konfig Skalier HW-Abgleich
Each channel is calibrated ex-works in order to correct component dis-
persion and other influences.
The range is divided so that zero is assigned the value 0 and the end
point is assigned the value 4095
D
(0FFF
H
).
4.2.1.3
Manufacturer scaling
Manufacturer scaling
4-
][Funktionsbeschreibung_BA_Konfig Skalier Herst. Ein
The manufacturer scaling is used to define the offset (zero point com-
pensation) and gain (amplification) of the digital signal.
Manufacturer scaling active (default setting)
Default values for manufacturer scaling:
– Offset (b
1
): 0
– Gain (a
1
): 8194
D
(2002
H
)
INFORMATION
The default setting for gain (a
1
) means an amplification factor of
8.